background image

20

£

Special Note

1.

When changing the 

24CJ5, Model 3000 to the 70D30-71D80-72DRT1
24CU6 Model 1050 to the 70D30-71D80-72DUV1
26CF6, Model 1000 to the 70D30-71D80-72DIR1 

do the following:

— Replace the wiring base with P/N 60-1386-2 or P/N 60-1466-2.
— Replace wires on corresponding terminals except as noted below.
— The existing STARTING INTERLOCK circuit (3 to D) must be changed to M to D.
— The existing RUNNING INTERLOCKS remain between 3 and P.

IMPORTANT: The STARTING INTERLOCKS and RUNNING INTERLOCKS must be
isolated from one another.

FIGURE 5.

COMPLETED CONVERSION

2.

When changing the 

24CJ5, Model 3010 or 3011 to the 70D30-71D80, 71D90-72DRTI
25CU6, model 1062 or 1063 to the 70D30-71D80, 71D90-72DIR1 

do the following:
— Replace the wiring base with P/N 60-1386-2 or P/N 60-1466-2.
— Replace wires on corresponding terminals.

MAINTENANCE

Type 48PT2 Infrared and Type UV1, UV8A, UV2, and 45UV5-1009 UltraViolet Scanners

The viewing area of the scanner must be kept clean. Even a small amount of contamination will
reduce the flame signal reaching the detector by a measurable amount. Wipe the viewing area rou-
tinely using a soft cloth dampened with concentrated detergent.

Type 48PT2 scanners include a replaceable #4-263-1 Firetron cell.
Type 45UV5-1009 scanners include a replaceable #4-314-1 UV tube.

Type 69ND1 Flame Rod.

 The flame rod and its insulator should be kept clean by washing routinely

with soap and water. Rods should be routinely replaced as they oxidize.

Flame Signal Strength.

 Routine observation of the flame signal strength on a DC test meter plugged

into the test jack of the Amplifier will forewarn of any deterioration in the capability of the flame
detector or its application.

Contacts.

 There are no accessible contacts in the Fireye D30 Series control. Where contacts are

used, their design assures long trouble-free life when the load circuits are maintained within the pub-
lished load ratings.

Humidity.

 In areas of high humidity, the control chassis should be removed and placed in a dry

atmosphere when the system is expected to be out of service for an extended period.

Periodic Safety Check.

 A procedure should be established to test, at least once a month, the com-

plete flame safeguard system. This test should verify the proper operation of all limit switches and
safety interlocks as well as flame failure protection and fuel safety shutoff valve tightness.

Rotation.

 It is recommended that control and scanner units purchased as spares be installed periodi-

cally.

P

D

M

3

RUNNING

INTERLOCK

STARTING

INTERLOCK

TO MOTOR

FROM LIMITS

Summary of Contents for D30 Series

Page 1: ...ed during the prepurge and firing period The control system de energizes all fuel valves within four seconds following flame failure An alarm circuit actuates audible and visual alarms following a saf...

Page 2: ...F C UV1A UV2 UV8A UV90 Scanner 200qF 93qC 40qF C 45UV5 Scanner 200qF 93qC 40qF C 48PT2 Scanner 140qF 60qC 40qF C 69ND1 Flame Rod TIP 2460qF 1500qF 816qC 40qF C Humidity 85 RH MAX NON Condensing MAXIMU...

Page 3: ...cable UV8A 90q head 1 2 NPT mount 72 unshielded leads UV90 3 6 9 90 side opening 36 900mm 72 1800mm or 108 2700mm cable 45UV3 1050 3 4 mount cast aluminum housing 8 wire 72DUVS4 Ultraviolet Repetitive...

Page 4: ...application of a control could result in an unsafe condition hazardous to life and property Selection of a control for a particular application should be made by a compe tent professional such as a bo...

Page 5: ...semble or disassemble a control and its plug in modules place the unit on a work bench remove the two module retainer hold down screws and lift off the module retainer The module retainer cannot be re...

Page 6: ...r a short circuit is detected it must be eliminated before the control is plugged into the wiring base and power turned on Otherwise the control may be destroyed or improper operation may occur INSTAL...

Page 7: ...ield of view 5 CAUTION The scanner must not sight the ignition spark directly or any part of the burner that can reflect the spark back to the scanner The scanner must not see a pilot flame that is to...

Page 8: ...g UV Scanners To connect the scanner to the control the UV1 and UV8A scanners are supplied with 36 or 72 of flexible cable The UV2 comes with 36 of flexible cable to connect the scanner to the control...

Page 9: ...t flame too short or in the wrong position to ignite the main flame reliably must not be detected 4 Scanner must have unobstructed view of flame being monitored 5 Flame being monitored must completely...

Page 10: ...d at least 1 2 into the flame but not more than half way through 5 If the flame is partly luminous the electrode tip should extend only to the edge of the flame It is not necessary to maintain absolut...

Page 11: ...llows 7 Following a 10 second trial for ignition if the flame is detected the main fuel valve Terminal 7 is energized and the TFI indicator LED goes out 8 Ten seconds later Terminal 5 de energizes the...

Page 12: ...ch mounted on the main fuel valve and activated by the valve stem It is connected between Terminal 3 and 13 The valve proof of closure interlock prevents a burner start up if the valve stem is not in...

Page 13: ...eck all safety interlocks for proper shut down of the boiler To measure the Series D30 control s flame signal strength use a 1 000 ohm volt or greater DC volt meter or a Digital meter with input imped...

Page 14: ...the control will de energize the pilot assembly at the end of the trial for ignition interval and the control will lockout The check run switch must be in the run position for this test FIGURE 3 TYPI...

Page 15: ...lot test must be accomplished by a trained and qualified burner technician 1 Manually turn off the main fuel supply 2 Place the check run switch in the check position 3 Turn power on and initiate a no...

Page 16: ...and low fuel pressure or temperature switches low fire start switches fuel valve proof of closure interlock etc 4 Pilot flame failure response and lockout 5 Main flame failure response and lockout 6...

Page 17: ...y 560 volts AC for 72DUV1 72DUVS4 and 72DUVSIT amplifiers 7 volts DC for 72DIRI amplifier and 280 volts AC for 72DRT1 amplifier with power on and burner off Before troubleshooting check the following...

Page 18: ...ting actual flame Replace flame scanner or correct scanner wiring Replace 72D series amplifier module Replace 70D30 control Pilot not energized at the end of purge Air Flow indicator on TFI and FIREYE...

Page 19: ...Pilot flame does not shut off following main flame TFI Pilot connected to terminal 5 Air flow Fireye indicators on Pilot valve stuck open Wiring error Replace 70D30 control Flame signal drops off whi...

Page 20: ...canners include a replaceable 4 263 1 Firetron cell Type 45UV5 1009 scanners include a replaceable 4 314 1 UV tube Type 69ND1 Flame Rod The flame rod and its insulator should be kept clean by washing...

Page 21: ...direct connection of limit and operating controls Fuel valve interlock low fire start interlock running interlocks such as air flow fuel pressure and temperature and Burner Motor Ignition Main fuel v...

Page 22: ...IPE THREAD 1 DIA 25 4 UV1A UV SCANNER 36 FLEXIBLE CABLE UV 1A 3 72 FLEXIBLE CABLE UV 1A 6 72 LEAD 2 7 8 73 2 50 8 1 5 8 41 3 1 4 82 UV SCANNER Type 45UV3 Model 1050 2 3 8 60 3 2 3 8 60 3 1 2 12 7 L 1...

Page 23: ...23...

Page 24: ...s found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND F...

Reviews: