132
MS-9600LS Series Manual —
P/N 52646:B2 2/12/2010
Programming
Master Programming Level
ANN-S/PG (Print) Options
The Print option allows the programmer to configure the optional printer. Pressing 1 while viewing
ANN-BUS screen #2 will display the following screens:
Pressing
1
for Port while viewing ANN-S/PG Options screen #1 will allow the programmer to
select between a Parallel and Serial Port for printer connection. Each press of the
1
key will cause
the display to toggle between
Port PAR
(parallel) and
Port SER
(serial). It is important to note that
the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an
offline timer for the supervision by pressing
2
for Printer Supervision while viewing Print Options
screen #1. Each press of the
2
key will cause the display to toggle between
Printer Supv NO
for no
supervision and
Printer Supv YES
for printer supervision. Note that this option is not selectable if
the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an
Offline Timer
by pressing
3
while viewing Print Options screen #1. The resultant screen allows the programmer to program
the
Offline Timer
for a delay of between 0 and 255 seconds before loss of printer supervision is
reported as a trouble.
If the Serial Port option is selected, the
Printer Supv
and
Offline Timer
options will not be available.
The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port
option has been selected.
Pressing
1
for
Baud Rate
while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of
19200, 9600, or 2400
.
Pressing
2
for
Data Bits
while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select
7
or
8 Data Bits
.
Pressing
3
for
Parity
while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select between
No Parity
,
Even Parity,
or
Odd Parity
.
Pressing
1
for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear
which allows the user to select between
1.0
or
2.0 Stop Bits
.
ANN-BUS
1=ANN-S/PG OPTIONS
2=ANN-80 OPTIONS
ANN-BUS Screen #2
ANN-S/PG OPTIONS
1=PORT PAR
2=PRINTER SUPV NO
3=OFFLINE TIMER 60
ANN-S/PG Options Screen #1
ANN-S/PG OPTIONS
1=BAUD RATE N/A
2=DATA BITS N/A
3=PARITY N/A
ANN-S/PG Options Screen #2
ANN-S/PG OPTIONS
1=STOP BITS N/A
ANN-S/PG Options Screen #3