Read Status
4.22.3 Power
Pressing
3
while viewing Read Status Screen #1 will display the following screens:
A real-time display of control panel voltages can be used to determine if system problems exist.
Note that Zones Screen #3 will only be displayed if the NACKEY NAC option card is installed, in
JP8 of the main circuit board, for Class B operation.
The following table lists the circuit being measured, possible conditions and their respective volt-
age ranges:
Circuit
Condition
Voltage Range
Battery
Normal Battery (nominal)
27.05 to 28.15 VDC
Low Battery
20.0 to 20.8 VDC
No Battery
0 to 18.36 VDC
24V Resettable
Normal
21.25 to 27.50 VDC
24V Nonresettable
Normal
21.25 to 27.50 VDC
Charger
Normal
27.05 to 28.15 VDC
NACs
Normal
-1.3 to -1.6 VDC
Open Circuit
-2.3 to -2.5 VDC
Short Circuit
0 to 1.0 VDC
POWER
BATTERY 27.21V
24 V RST 25.31V
Zones Screen #1
POWER
CHARGER 28.36V
NAC 1 -2.39V
NAC 2 -2.39V
Zones Screen #2
POWER
NAC 3 -2.39V
NAC 4 -2.39V
Zones Screen #3