88
MS-9600LS Series Manual —
P/N 52646:B2 2/12/2010
Programming
Master Programming Level
Edit Module Screen for Control Modules
The programmer can change a module’s existing or factory default programming by pressing
3
in
the Modules Screen. The following screen will be displayed:
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as
002
. When the last digit is keyed
in, if the selected address corresponds to a
control
module, a screen displaying information about
the control module with the selected address will be displayed as illustrated in the following:
In the preceding example:
•
Normal - indicates that the module with the selected address is physically installed on the SLC
and communicating with the control panel (enabled).
•
<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device.
•
Control - indicates that the selected module is a control module.
•
S or * - represents Silenceable (S) or Nonsilenceable (*).
•
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled).
•
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 099).
•
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop 1, M=Module
and 002 = Module Address 02).
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
EDIT MODULE
ENTER MODULE ADDRESS
***
Edit Module Screen
NORMAL CONTROL
<ADJ><NOUN>
SW ZNNN
1M002
Edit Control Screen #1