18
MS-9600LS Series Manual —
P/N 52646:B2 2/12/2010
Product Description
Circuits
•
Maintenance/presignal (yellow)
•
Alarm Silenced signals (yellow)
•
Disabled (yellow)
•
Battery fault (yellow)
•
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•
Acknowledge/Step
•
Alarm Silence
•
Drill
•
Reset (lamp test)
Service/program keys:
•
Keys labeled 1 to 9
•
* key
•
# key
•
0 (recall) key
•
1st Event key
•
Clear key
•
Escape key
•
Mode key
•
Four cursor keys (up, down, left and right)
•
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.
1.5 Circuits
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. A second SLC loop is avail-
able by plugging the optional SLC module into connector J3 on the main circuit board. SLC loops,
configurable for NFPA Style 4, 6 or 7, provide communication to addressable detectors, monitor
(initiating device) and control (output device) modules. Refer to the SLC Wiring Manual for infor-
mation on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
•
Special Application Power
• 24 VDC Resettable (smoke detector power) output - 1.5 amps maximum
• 24 VDC Nonresettable power output #1 - 1.5 amps maximum
• 24 VDC Nonresettable power output #2 - 1.5 amps maximum
•
24 VDC Battery Charger (up to 26 AH batteries)
Figure 1.2 Membrane/Display Panel