64
MS-9600LS Series Manual —
P/N 52646:B2 2/12/2010
Programming
Programming and Passwords
Change” on page 135. If an invalid password is entered, the blinking cursor will return to the first
password character position. To exit Programming or Read Status mode at any time, press the
ESC
(Escape) key repeatedly. Note that Programming mode must be exited using the
ESC
key in order
to store the program data entered during this mode. If the
Reset
key is pressed or power is lost
before exiting Programming mode, the data just entered will not be saved.
To access user Programming mode, press the
Enter
or
Mode
key. The LCD will display the follow-
ing:
To enter the user Programming mode, press
2
. The display will read as follows:
Entering the
Master
level password (default
00000
) will cause the following screen to appear:
If the
Maintenance
level password (default
11111
) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad
down
arrow key.
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
PROGRAMMING
ENTER PASSWORD
*****
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK