![Festo IFB05-03 Manual Download Page 52](http://html1.mh-extra.com/html/festo/ifb05-03/ifb05-03_manual_2284204052.webp)
3. Installation
3−18
Festo P.BE−VIFB5−03−EN en 0503e
3.3.2 Connecting the power supply
The following separate supplies of +24V DC are provided via
the power supply connection:
the operating voltage for the internal electronics and the
inputs of the input modules (pin 1: +24 V DC, tolerance
±25%, external fuse M3.15A recommended).
the load voltage for valve outputs and outputs of the out
put modules (pin 2: +24 V DC, tolerance ±10%, external
fuse max. 10 A (slow blowing) required).
1
Power supply for
type 03
2
Power supply for
type 04B
ÓÓ
ÓÓ
Ó
1
2
Fig.3/9: Type−specific power supply connection
Please note
Check within the framework of your EMERGENCY STOP
circuit, to ascertain which measures are required for put
ting your machine/system in a safe state in the event of an
EMERGENCY STOP (e.g. switching off the load voltage for
the valves and output modules, switching off the pres
sure).
Summary of Contents for IFB05-03
Page 2: ......
Page 15: ...Summary of components 1 1 Festo P BE VIFB5 03 EN en 0503e Chapter 1...
Page 24: ...1 Summary of components 1 10 Festo P BE VIFB5 03 EN en 0503e...
Page 25: ...Fitting 2 1 Festo P BE VIFB5 03 EN en 0503e Chapter 2...
Page 35: ...Installation 3 1 Festo P BE VIFB5 03 EN en 0503e Chapter 3...
Page 63: ...Commissioning 4 1 Festo P BE VIFB5 03 EN en 0503e Chapter 4...
Page 95: ...Diagnosis and error treatment 5 1 Festo P BE VIFB5 03 EN en 0503e Chapter 5...
Page 126: ...5 Diagnosis and error treatment 5 32 Festo P BE VIFB5 03 EN en 0503e...
Page 127: ...Technical appendix A 1 Festo P BE VIFB5 03 EN en 0503e Appendix A...
Page 141: ...Accessories B 1 Festo P BE VIFB5 03 EN en 0503e Appendix B...
Page 146: ...B Accessories B 6 Festo P BE VIFB5 03 EN en 0503e...
Page 147: ...Index C 1 Festo P BE VIFB5 03 EN en 0503e Appendix C...
Page 148: ...C Index C 2 Festo P BE VIFB5 03 EN en 0503e Contents C Index C 1...