A. Technical appendix
A−11
Festo P.BE−VIFB5−03−EN en 0503e
Formula for cable length:
L
v
(V
Bmin
− 21.6V)
· A ·
κ
CU
2
I
2
+ I
1
This means:
21.6 V V
VALVE TERMINAL
= 24 V ± 10%, minimum:
w
21.6 V
V
Bmin
= minimum supply voltage
(at the power unit)
l
1
= current for electronics and inputs
I
2
= current for outputs/valves
A = cable cross−sectional area (uniform e.g. 1.5 mm
2
)
κ
= conductance value of cables
(uniform e.g.
κ
Cu
= 56
m
mm
2
·
Ω
Example:
I
1
=
1 A
I
2
=
5 A
V
Bmin
=
24 V
V
VALVE TERMINALmin
= 21.6 V
κ
Cu
=
56
m
mm
2
·
≅
Ω
Result of example:
L
v
18 m for A = 1.5 mm
2
L
v
30 m for A = 2.5 mm
2
Summary of Contents for IFB05-03
Page 2: ......
Page 15: ...Summary of components 1 1 Festo P BE VIFB5 03 EN en 0503e Chapter 1...
Page 24: ...1 Summary of components 1 10 Festo P BE VIFB5 03 EN en 0503e...
Page 25: ...Fitting 2 1 Festo P BE VIFB5 03 EN en 0503e Chapter 2...
Page 35: ...Installation 3 1 Festo P BE VIFB5 03 EN en 0503e Chapter 3...
Page 63: ...Commissioning 4 1 Festo P BE VIFB5 03 EN en 0503e Chapter 4...
Page 95: ...Diagnosis and error treatment 5 1 Festo P BE VIFB5 03 EN en 0503e Chapter 5...
Page 126: ...5 Diagnosis and error treatment 5 32 Festo P BE VIFB5 03 EN en 0503e...
Page 127: ...Technical appendix A 1 Festo P BE VIFB5 03 EN en 0503e Appendix A...
Page 141: ...Accessories B 1 Festo P BE VIFB5 03 EN en 0503e Appendix B...
Page 146: ...B Accessories B 6 Festo P BE VIFB5 03 EN en 0503e...
Page 147: ...Index C 1 Festo P BE VIFB5 03 EN en 0503e Appendix C...
Page 148: ...C Index C 2 Festo P BE VIFB5 03 EN en 0503e Contents C Index C 1...