7
Diagnostics
Festo – EXCM-10/-30-...-E-EN – 1612b – English
67
Hex
Type of error/diagnostic memory
Error name
Dec
26
38
CAN fieldbus parameters missing
(CAN fieldbus parameters missing)
Can be parameterised as:
F
/-/-
Diagnostic memory: always
One or more CAN bus parameters are not correct.
Check the CAN bus parameters.
–
Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s):
B
27
39
Save parameters
(Save parameters)
Can be parameterised as:
F
/-/-
Diagnostic memory: optional
Error when writing the internal flash memory.
Execute the last operation again. If the error continues to occur, the hardware may be defective.
–
Acknowledgement option: Error can only be acknowledged after the cause is eliminated.
Parameterisable error response(s):
G
28
40
Homing required
(Homing required)
Can be parameterised as:
F
/-/-
Diagnostic memory: optional
A valid homing run has not yet been executed.
The reference point is no longer valid (e.g. through logic voltage failure or because the axis zero point
has been changed).
Perform a homing run or repeat the last homing run if it was not completed successfully.
–
Acknowledgement option: Error can only be acknowledged after the cause is eliminated.
Parameterisable error response(s):
B
, C, D, E, F, G
29
41
Target position behind negative software end
position
(Target position behind negative software end
position)
Can be parameterised as:
F
/-/-
Diagnostic memory: optional
The start of a positioning process was suppressed as the target is past the relevant software limit
switch.
Check the target data.
Check positioning area.
Check type of travel record (absolute/relative)
–
Acknowledgement option: Error can only be acknowledged after the cause is eliminated.
Parameterisable error response(s):
B
, C, E, F