3
Installation
Festo – P.BE-CPX-CTEL-EN – 1411a – English
19
3.2
Mounting and dismantling of the module
The CTEL master module is designed for mounting in a CPX interlinking block (
è
Warning
Mounting/dismantling of the CTEL master module must always take place in a de-ener
gised state.
Disconnect the corresponding CPX terminal completely from the related power sup
ply or switch it off.
Note
The CTEL master module does not have a separate connection block, but is designed as
a complete unit.
Before the CTEL master module is mounted, the desired operating mode/configuration
should be set or checked with the help of the DIL switches (
è
longer be reached after mounting.
3
2
1
4
1
CTEL master module
2
Interlinking block (here with additional
power supply, as an example)
3
Contact rails
4
Screws
Fig. 3.1
Summary of Contents for CPX-FB13
Page 62: ......