2
System overview, CTEL system
Festo – P.BE-CPX-CTEL-EN – 1411a – English
15
2.4
Addresses
The CTEL master module can make available a total of up to 32 bytes for inputs and 32 bytes for out
puts. The precise amount of the I/O bytes made available depends on the requirements of the connec
ted devices or of the correspondingly selected operating mode.
2.4.1
I/O configuration presettings
The address space that the CTEL master module makes available and assigns accordingly in the CPX
system can be configured according to 13 different presettings (
è
Tab. 2.4). These presettings corres
pond to the selection options that are supported within the configuration files for the respective host
system (
è
There are 4 presettings available in each case for operation as “pure input module”, “pure output mod
ule” and for “mixed operation”.
In addition, there is a configuration for operation without connected devices.
Operation as
Unused module
0 bytes
0 bytes
Pure output module
0 bytes
8 bytes
0 bytes
16 bytes
0 bytes
24 bytes
0 bytes
32 bytes
Pure input module
8 bytes
0 bytes
16 bytes
0 bytes
24 bytes
0 bytes
32 bytes
0 bytes
Mixed operation
8 bytes
8 bytes
16 bytes
16 bytes
24 bytes
24 bytes
32 bytes
32 bytes
1)
Related to the complete CTEL master module
2)
Only available in automatic configuration
Tab. 2.4
The I/O lengths listed here are the sum of the bytes available for all I-ports together.
Which of these configuration presettings the CTEL master module uses can be determined manually
(through the user) or automatically (through the module itself ), dependent on the operating mode.
Summary of Contents for CPX-FB13
Page 62: ......