If there is a short circuit, the input module will switch off
the power supply to the sensors and lock them in this
state. It will also communicate the error to the higher-
order system. The status LEDs will be switched off and
the inputs of the module will transmit a 0-signal. When
the short circuit has been eliminated, you can delete
this error as follows:
Short circuit
in sensor
supply
In conjunction with the CP field bus node:
••
Disconnect the input module briefly from the line, or
••
switch off the power supply at the node and then
switch it on again.
In conjunction with the SPC200:
••
Proceed as described in the user manual type
P.BE-SPC200.
If there is a fault in the CP module during operation,
you can replace the module with one of the same type,
even during operation.
Replacing
the CP
module
PLEASE NOTE
Observe here the instructions in the manual for the
higher-order system (e.g. CP system, CP field bus
node, SPC200).