1.3.2 Connecting the input module
WARNING
Please observe the maximum permitted string
lengths in each case. You will then avoid faults in
data exchange between the input module and the
higher-order system (e.g. the field bus node).
Use only the following cables for connecting the
modules:
For connection to
Max. permitted
string length
Cable type
Field bus node
with CP connection
10 m
- KVI-CP-1-...
or
- KVI-CP-2-...
(can be used as
drag chain)
Axis interface
type SPC-AIF-...
See manual for
SPC200 type
P.BE-SPC200-...
Powerbox
type CP-FB-TBOX-
...
See manual for
higher-order
system
By means of the CP cable the module is supplied with
the following:
– operating voltage for the internal electronic compo-
nents
– operating voltage for the connected sensors
– connection for data exchange.
1. Input module type CP-E16...-M...-...
1-20
CP-E16...-M... 9901b