Protection devices HIGH PRESSURE
Through the accessory interface RS485 MODBUS ® RTU control system is able to communicate with the outside world. The outside
world means a master device, usually a supervisory system or a BMS (Building Management System), designed by the customer.
SERIAL INTERFACE: RS485 MODBUS® RTU
CAUTION :
The use of serial communication must be made by qualified personnel.
The company assumes no responsibility for any damage to the machine due to misuse of the serial interface.
Modbus RTU
RS485
chiller
MASTER
SLAVE
supervisor
BMS
Communication with the machine is with
MODBUS ® RTU on RS485 serial network.
RS485 settings of the chiller
Serial communication with the chiller is only possible if
you installed accessory: interface RS485 MODBUS ®
RTU.
The default parameters of MODBUS ®-RTU are:
Serial address of chiller
1
Protocol
MODBUS®-RTU
Baud rate
9600 b/s
Parity
EVEN
MODBUS ® Address Table: Machine Level
(*)
Type of variable/parameter:
A= Analog; D = Digital; I = Integer
Parameter/Description
Def
Min
Max U.M. Type
(*)
Decimal
Position Modbus
Modbus
HEX
R/W Notes/Meaning
Chiller on/off
D
340
0154
R/W
Chiller mode
0
3
I
0
1520
05F0
R
0 = standby
1 = cooling
2 = hot
3 = shut down
Chiller capacity
0
100
%
I
0
1524
05F4
R
Evaporator water inlet temperature
-50.0
150.0
°C
A
1
1522
05F2
R
Evaporator water outlet temperature
-50.0
150.0
°C
A
1
1523
05F3
R
Setpoint 1 chiller mode
7.0
5.0
-8.0 (**)
20.0
°C
A
1
624
0270
R/W (**) for brine unit
Band 1 chiller mode
1.0
0.5
5.0
°C
A
1
628
0274
R/W
Setpoint 2 chiller mode
7.0
5.0
-8.0 (**)
20.0
°C
A
1
635
027B
R/W (**) for brine unit
Band 2 chiller mode
1.0
0.5
5.0
°C
A
1
638
027E
R/W
Setpoint 1 heatpump mode
45.0
30.0
55.0
°C
A
1
656
0290
R/W
Band 1 heatpump mode
1.0
0.5
3.0
°C
A
1
660
0294
R/W
Setpoint 2 heatpump mode
45.0
30.0
55.0
°C
A
1
667
029B
R/W
Band 2 heatpump mode
1.0
0.5
3.0
°C
A
1
670
029E
R/W
Current setpoint
-50.0
150.0
°C
A
1
1518
05EE
R
Heat recovery water inlet temperature
-50,0
150,0
°C
A
1
1381
0565
R
Heat recovery enable function
1
0
1
D
0
1199
04AF
R/W 0 = not enabled
1 = enabled
Heat recovery setpoint temp
42,5
32,0
53,0
°C
A
1
1202
04B2
R/W
Heat recovery prop band
5,0
4,0
10,0
°C
A
1
1203
04B3
R/W
ALARM Chiller general
0
0
2
I
0
1519
05EF
R
0 = not active
1 = active
2 = resettable
ALARM Plant high temperature
0
0
2
I
0
1245
04DD
R
ALARM Plant low temperature
0
0
2
I
0
1246
04DE
R
ALARM Evaporator freezing
0
0
3
I
0
1290
050A
R
0 = not active
1 = automatic
2 = resettable
3 = active
ALARM Evaporator water flow
0
0
3
I
0
1292
050C
R
ALARM Phase sequence
0
0
3
I
0
1371
055B
R
ALARM Heat recovery water flow
0
0
3
I
0
1247
04DF
R
ERROR water inlet probe
0
0
1
I
0
1335
0537
R
0 = active
1 = not active
ERROR water outlet probe
0
0
1
I
0
1325
052D
R
ERROR external air probe
0
0
1
I
0
1375
055F
R
ERROR Heat recovery Inlet Water probe
0
0
1
I
0
1372
055C
R