GENERAL SPECIFICATIONS - VERSION wITH DESUPERHEATER (VD)
IR COOLING UNIT ONLY
(1):
The data refer to: Water temperature: evaporator inlet
:12°C
- evaporator outlet:
7°C,
Outdoor air temperature
35°C
.
The data refer to: Water temperature: recovery inlet :
40°C
- recovery outlet:
45°C.
Acoustic Version: AB (Standard Unit)
Recovery heat exchanger specifications
(1):
The data refer to: Water temperature: evaporator inlet
:12°C
- evaporator outlet:
7°C,
Outdoor air temperature
35°C
.
The data refer to: Water temperature: recovery inlet :
40°C
- recovery outlet:
45°C.
Acoustic Version: AS (Low noise Unit)
Recovery heat exchanger specifications
(1):
The data refer to: Water temperature: evaporator inlet
:12°C
- evaporator outlet:
7°C,
Outdoor air temperature
35°C
.
The data refer to: Water temperature: recovery inlet :
40°C
- recovery outlet:
45°C.
Acoustic Version: AX (Extra low noise Unit)
Recovery heat exchanger specifications
MODEL
350.5
390.6
440.6
490.6
560.6
630.6
UM
Type of recovery exchanger
Brazed plates
-
Quantity
1
N°
Max. operating pressure on wet side
600
kPa
Total water content of recovery exchangers
1.3
1.3
1.3
1.3
1.3
1.3
l
Unit specification
Cooling capacity VD(1)
365
389
457
514
581
650
kW
Power input compressor VD (1)
102
110
128
147
163
186
kW
Total power input VD (1)
117
125
146
165
184
207
kW
EER VD (1)
3.12
3.11
3.13
3.12
3.16
3.14
-
Water flow rate VD (1)
17.5
18.6
21.8
24.6
27.8
31.0
l/s
Water pressure drop VD (1)
56
58
62
65
63
60
kPa
Recovered heating capacity (1)
87.7
93.4
110
123
139
156
kW
Recovered water flow rate (1)
4.19
4.46
5.26
5.88
6.64
7.45
l/s
Recovered water pressure drop (1)
24
27
25
32
31
39
kPa
MODEL
350.5
390.6
440.6
490.6
560.6
630.6
UM
Type of recovery exchanger
Brazed plates
-
Quantity
1
N°
Max. operating pressure on wet side
600
kPa
Total water content of recovery exchangers
3.8
3.8
3.8
3.8
3.8
3.8
l
Unit specification
Cooling capacity VD(1)
350
373
438
493
557
624
kW
Power input compressor VD (1)
110
119
137
158
176
200
kW
Total power input VD (1)
124
134
155
176
197
221
kW
EER VD (1)
2.82
2.78
2.83
2.80
2.83
2.82
-
Water flow rate VD (1)
16.7
17.8
20.9
23.6
26.6
29.8
l/s
Water pressure drop VD (1)
51
53
57
60
58
56
kPa
Recovered heating capacity (1)
87.7
93.4
110
123
139
156
kW
Recovered water flow rate (1)
4.19
4.46
5.24
5.90
6.66
7.45
l/s
Recovered water pressure drop (1)
24
27
25
32
31
39
kPa
MODEL
350.5
390.6
440.6
490.6
560.6
630.6
UM
Type of recovery exchanger
Brazed plates
-
Quantity
1
N°
Max. operating pressure on wet side
600
kPa
Total water content of recovery exchangers
3.8
3.8
3.8
3.8
3.8
3.8
l
Unit specification
Cooling capacity VD(1)
343
366
430
483
546
612
kW
Power input compressor VD (1)
113
123
141
163
180
206
kW
Total power input VD (1)
128
138
159
181
202
227
kW
EER VD (1)
2.68
2.65
2.70
2.67
2.70
2.70
-
Water flow rate VD (1)
16.4
17.5
20.5
23.1
26.1
29.2
l/s
Water pressure drop VD (1)
49
51
55
58
56
53
kPa
Recovered heating capacity (1)
87.7
93.4
110
123
139
156
kW
Recovered water flow rate (1)
4.19
4.46
5.26
5.88
6.64
7.45
l/s
Recovered water pressure drop (1)
24
27
25
32
31
39
kPa