23
STANDARD PERFORMANCES - IP HEAT PUMP UNITS
Performances in cooling mode - Standard Unit AB
Tw=
Outlet water temperature °C
kWf
= Cooling capacity (kW).
kWa
= Compressor power input (kW)
The standard performances refer to a 5°C temperature difference between the water entering and leaving the heat exchanger and to operation of the unit with all fans at
nominal or maximum speed. A 0.44 x 10
-4
m
2
K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
The performances are declared no considering any correction due to water flow rate and water side pressure drop (gross performance).
MOD.
Tw
OUTDOOR AIR TEMPERATURE (°C D.B.)
20
25
30
35
40
45
50 (2)
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
350.5
5
389
73.0
363
84.0
344
92.5
322
102
300
112
278
123
255
133
6
400
73.7
373
84.7
353
93.4
331
103
308
113
286
124
262
134
7
412
74.4
384
85.6
363
94.3
341
104
317
115
294
125
270
135
8
423
75.2
395
86.6
374
95.4
351
105
326
116
302
126
-
-
9
435
76.0
406
87.4
384
96.3
360
106
335
117
310
128
-
-
10
447
76.7
417
88.3
394
97.3
370
107
344
118
319
129
-
-
11
458
77.5
427
89.2
404
98.2
379
108
353
119
327
130
-
-
12
470
78.2
439
90.0
415
99.2
390
109
363
121
336
131
-
-
390.6
5
415
78.6
388
90.4
367
99.6
344
110
320
121
297
132
272
143
6
427
79.3
399
91.3
377
101
354
111
329
122
305
133
280
144
7
439
80.1
410
92.2
388
102
364
112
339
123
314
135
288
146
8
452
81.0
422
93.2
399
103
374
113
348
125
323
136
-
-
9
464
81.8
433
94.2
410
104
385
114
358
126
331
137
-
-
10
477
82.6
445
95.1
421
105
395
116
367
127
340
139
-
-
11
489
83.5
456
96.0
431
106
405
117
377
129
349
140
-
-
12
502
84.3
469
97.0
443
107
416
118
387
130
358
142
-
-
440.6
5
486
91.2
454
105
429
116
403
127
375
141
347
153
319
166
6
500
92.1
466
106
441
117
414
129
385
142
357
155
328
167
7
514
93.0
480
107
454
118
426
130
396
143
367
156
337
169
8
529
94.0
494
108
467
119
438
131
408
145
377
158
-
-
9
543
95.0
507
109
480
120
450
133
419
146
388
160
-
-
10
558
95.9
521
110
492
122
462
134
430
148
398
161
-
-
11
572
96.9
534
111
505
123
474
135
441
149
408
163
-
-
12
588
97.8
549
113
519
124
487
137
453
151
419
164
-
-
490.6
5
548
105
511
120
484
133
454
146
422
161
391
176
359
190
6
563
106
526
121
497
134
466
147
434
163
402
177
369
192
7
579
107
541
123
511
135
480
149
447
164
414
179
380
194
8
596
108
556
124
526
137
494
151
459
166
425
181
-
-
9
612
109
572
125
540
138
507
152
472
168
437
183
-
-
10
629
110
587
126
555
139
521
154
484
169
449
185
-
-
11
645
111
602
128
569
141
534
155
497
171
460
186
-
-
12
662
112
618
129
584
142
548
157
510
173
473
188
-
-
560.6
5
616
116
575
134
544
148
511
163
475
179
440
196
404
212
6
633
118
591
135
559
149
525
164
488
181
452
197
415
213
7
652
119
609
137
575
151
540
166
502
183
465
199
427
216
8
670
120
626
138
592
152
555
168
517
185
479
202
-
-
9
689
121
643
140
608
154
571
170
531
187
492
204
-
-
10
707
122
660
141
624
155
586
171
545
189
505
206
-
-
11
725
124
677
142
640
157
601
173
559
191
518
208
-
-
12
745
125
695
144
657
158
617
175
574
192
532
210
-
-
630.6
5
694
133
648
153
613
168
575
185
535
204
495
223
455
241
6
713
134
666
154
630
170
591
187
550
206
509
225
468
243
7
734
135
685
156
648
171
608
189
566
208
524
227
481
246
8
755
137
705
157
666
173
625
191
582
211
539
230
-
-
9
776
138
724
159
685
175
642
193
598
213
554
232
-
-
10
796
139
743
160
703
177
659
195
614
215
568
234
-
-
11
817
141
762
162
721
179
676
197
629
217
583
237
-
-
12
839
142
783
164
740
180
695
199
646
219
599
239
-
-
(1) :
at these temperatures the fans are at maximum speed.
(2) :
ATC (Advanced Temperature Control) function may occur.
Summary of Contents for RHA series