STANDARD PERFORMANCES - IR COOLING UNIT ONLY
Tw=
Outlet water temperature °C
kWf
= Cooling capacity (kW).
kWa
= Compressor power input (kW)
The standard performances refer to a 5°C temperature difference between the water entering and leaving the heat exchanger and to operation of the unit with all fans at
nominal or maximum speed. A 0.44 x 10
-4
m
2
K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
The performances are declared no considering any correction due to water flow rate and water side pressure drop (gross performance).
Performances - Standard unit AB
MOD.
Tw
OUTDOOR AIR TEMPERATURE (°C D.B.)
20
25
30
35
40
45 (1)
50 (1) (2)
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
350.5
5
401
73.7
374
84.8
354
93.4
332
103
309
113
286
124
263
134
6
412
74.4
384
85.6
363
94.3
341
104
317
115
294
125
270
135
7
424
75.1
396
86.4
374
95.2
351
105
327
116
302
126
278
136
8
436
76.0
407
87.4
385
96.3
361
106
336
117
311
128
-
-
9
448
76.7
418
88.3
395
97.3
371
107
345
118
320
129
-
-
10
460
77.5
429
89.1
406
98.2
381
108
354
119
328
130
-
-
11
471
78.2
440
90.0
416
99.2
390
109
363
121
336
131
-
-
12
484
79.0
452
90.9
427
100
401
110
373
122
346
133
-
-
390.6
5
427
80.0
398
92.0
377
101
354
112
329
123
305
134
280
145
6
439
80.7
410
92.9
387
102
363
113
338
124
313
136
288
147
7
452
81.6
421
93.8
399
103
374
114
348
126
322
137
296
148
8
464
82.5
433
94.9
410
105
385
115
358
127
331
139
-
-
9
477
83.3
445
95.8
421
106
395
116
368
128
341
140
-
-
10
490
84.1
457
96.8
432
107
406
118
377
130
350
141
-
-
11
502
84.9
469
97.7
443
108
416
119
387
131
359
143
-
-
12
516
85.8
482
98.7
455
109
427
120
398
132
368
144
-
-
440.6
5
501
91.9
468
106
442
117
415
128
386
142
358
154
329
167
6
515
92.8
481
107
455
118
427
130
397
143
368
156
338
168
7
530
93.7
495
108
468
119
439
131
408
144
378
157
347
170
8
545
94.8
509
109
481
120
451
132
420
146
389
159
-
-
9
560
95.7
523
110
494
121
464
134
432
147
400
161
-
-
10
575
96.7
537
111
507
123
476
135
443
149
410
162
-
-
11
590
97.6
550
112
520
124
488
136
454
150
421
164
-
-
12
606
98.6
565
113
535
125
502
138
467
152
432
166
-
-
490.6
5
564
106
526
122
498
134
467
148
435
163
402
178
370
192
6
579
107
541
123
511
136
480
149
447
165
414
180
380
194
7
596
108
557
124
526
137
494
151
460
166
426
181
391
196
8
613
109
572
126
541
138
508
153
473
168
438
183
-
-
9
630
110
588
127
556
140
522
154
486
170
450
185
-
-
10
647
111
604
128
571
141
536
156
499
172
462
187
-
-
11
663
113
619
129
586
143
550
157
511
173
474
189
-
-
12
681
114
636
131
601
144
564
159
525
175
486
191
-
-
560.6
5
637
118
595
136
562
149
528
165
491
182
455
198
418
214
6
655
119
611
137
578
151
542
166
504
183
467
200
429
216
7
674
120
629
138
595
152
558
168
519
185
481
202
442
218
8
693
122
647
140
611
154
574
170
534
187
494
204
-
-
9
712
123
664
141
628
156
590
172
549
189
508
206
-
-
10
731
124
682
143
645
157
605
173
563
191
522
208
-
-
11
749
125
699
144
661
159
621
175
578
193
535
210
-
-
12
770
126
718
145
679
160
638
177
593
195
549
212
-
-
630.6
5
713
134
666
154
630
170
591
187
550
206
509
225
468
243
6
733
135
684
156
647
171
607
189
565
208
523
227
481
246
7
755
137
704
157
666
173
625
191
581
211
539
230
495
248
8
776
138
724
159
685
175
643
193
598
213
554
232
-
-
9
797
140
744
161
704
177
660
195
614
215
569
234
-
-
10
818
141
764
162
722
179
678
197
631
217
584
237
-
-
11
839
142
783
164
741
180
695
199
647
219
599
239
-
-
12
862
144
805
165
761
182
714
201
664
221
615
241
-
-
(1) :
at these temperatures the fans are at maximum speed.
(2) :
ATC (Advanced Temperature Control) function may occur.