Basic settings
To put the controller into operation, please follow the steps outlined in these instructions.
9.1 Automatic query of basic data
If the controller is not already preconfigured by the door manufacturer, the following parameters are queried
automatically:
The DIP switch must have been turned on (see position DIP-switch figure Figure 43: DIP
switch position) so that the controller can query parameters automatically.
If DIP switch is not turned on and the basic parameters not set, error code F.090 is displayed.
The controller uses indicator "-1" or "-" in the display as a flag that the acquisition of this
parameter must be queried.
The basic data does not require changes when they were previously retrieved and set
automatically.
For help on operating the control, see Chapter
General operating instructions to set
•
Positioning system P.205
The limit switch system in use must be set using Parameter P.205.
P.205: 0000 = Mechanical limit switches Version 1 (Figure 28:: Connecting cam switches)
P.205: 0001 = Mechanical limit switches Version 2 (limit switches and pre-limit switches are normally
closed contacts)
P.205: 0300 = Absolute encoder DES-A (GfA)
P.205: 0700 = Absolute encoder DES-B (Kostal)
P.205: 0800 = Absolute encoder TST PD / TST PE (FEIG)
P.205: 0900 = Timer limit switches
•
Motor data P.100
– P.103
The door controller uses the following parameter setting to learn about the type of motor being used.
Read the data from the nameplate and enter them into the corresponding parameters.
Manufacturer
Type designation
0,5 KW
50 Hz
Iso.Kl.: F
IP 55
Figure 44: Typical motor nameplate (may vary)
Be sure to note the Y/
wiring of the motor. The motor data must be entered in accordance
with the motor wiring. 400 V setting is not applicable, since the controller can source a
maximum motor voltage of 230 V.
cos
0.85
P.101: Motor current
P.102: Cos
P.100: Nominal motor
frequency
P.103: Nominal motor voltage
/ Y 2.4 / 1.4 A
/ Y 230 / 400 V