FUZ2 -A/-B/-C/-CX/-G/-L
Assembly instructions
TST
FEIG ELECTRONIC GmbH
Page 62 of 96
TST_FUZ2-A-B-C-CX-G-L_Montageanleitung_EN_22.docx
8
General operating instructions to set parameters
8.1 Open the parameter operation mode
1.
Turn off the door controller and wait until the display has been completely extinguished.
2.
Open the cover of the enclosure and switch the DIP switch S500 (see illustration) to ON.
The service mode is activated and you can close the cover.
Figure 43: DIP switch position
The service mode is automatically reset after approx. 1 hour. In order to reach service mode again,
the controller must be turned off for a short period and then turned on again or a reset must be
performed.
3.
Close the cover of the enclosure and turn on the controller.
4.
+
Keep the keys pressed simultaneously to access the
parameter selection. (either appears
1: Clear text
display
or
2: 7-Segment display
)
P: Torzyklen |
000# 1234Zyk
P.
000
5.
or
Use the arrow keys to select the required parameter.
Not all the parameters are visible or may be changed
immediately; this always depends on the password and
the type of position set.
P: Offenhalt1 |
010= 10 s
P.
010
SERVICE
S500