- LDG ELEVATION - 10,000 FT
disappears.
5. On COMPT TEMP panel 437VU: On COMPT TEMP panel 437VU:
- reset BULK CARGO/ISOL - after isolation valve opens
VALVE (FWD CARGO/ISOL ISOL VALVE pushbutton switch FAULT
VALVE) pushbutton switch legend goes off.
6HN (52HN). On R ECAM display - AIR COND page:
- isolation valve opens and
color changes to green.
- hot trim air valve flap position
arrow remains at position C.
6. On CARGO COOL panel 444VU: On CARGO COOL panel 444VU:
- press BULK (FWD) pushbutton switch - ON legend comes on.
8OHN (78HN). On L ECAM display:
MEMO
BULK CARGO COOLING ON
(FWD CARGO COOLING ON)
appears.
On R ECAM display - AIR COND page:
- cold trim air valve flap
position arrow with scale appears.
7. On COMPT TEMP panel 437VU:
A310-200 AMM - CARGO COMPARTMENT
TEMPERATURE CONTROL - ADJUSTMENT/TEST
Revision 32.0
P.Blk EFFECTIVITY: FED ALL
21-64-00-05
Printed - Date: 12/11/12 Time:
Copyright © 12 FedEx Express Corporation, Memphis TN, 38194, All rights reserved.
Page 66 of 106
JUN 01/2012