- check that electrical power is - light comes on when pressed.
available at APU and pack temp
demand controller by pressing
BITE READY/UNPLUG CABLE AFTER
USE light.
- make certain that BITE SWITCH
is in position 1.
2. On circuit breaker panel 125VU:
- at location H65 open circuit
breaker 5HN.
- (at location H63 open circuit
breaker 43HN).
3. On BULK CARGO (FWD CARGO) compt
temp controller 15HN (54HN):
- remove BITE connector cap.
- connect test cable of APU
and pack temperature demand
controller 37HK to BITE connector.
4. On circuit breaker panel 125VU: On APU and pack temp demand
controller:
- at location H65 close circuit - BITE READY/UNPLUG CABLE AFTER
breaker 5HN. USE and GO indicator lights come
- (at location H63 close circuit on.
breaker 43HN).
5. On APU and pack temperature demand
controller:
- press NO GO indicator light. - NO GO integral light comes on.
- place BITE SWITCH to positions - for each position selected,
1 thru 12 in sequence, pausing GO indicator light must come on.
at each position until either
GO or NO GO light comes on.
NOTE : A NO GO light shows a failure
A310-200 AMM - CARGO COMPARTMENT
TEMPERATURE CONTROL - ADJUSTMENT/TEST
Revision 32.0
P.Blk EFFECTIVITY: FED ALL
21-64-00-05
Printed - Date: 12/11/12 Time:
Copyright © 12 FedEx Express Corporation, Memphis TN, 38194, All rights reserved.
Page 12 of 106
JUN 01/2012