SYSTEM PLANNING
47
assistance to properly place your warning
equipment.
The speakers connected to the UVIC may
be selectively turned on using amplifier
zones. Up to two zones may be
programmed into the UVIC to allow Zone
1, Zone 2 or all amp zones to be
activated. Amp Zones are programmed
using the AZ commands in SFCDWARE.
4.3 UVLOC
Placement
The UVLOC should be mounted in an
area that is readily accessible by all
potential operators. The console should
be clearly marked to identify its location.
Up to 10 Local Operation Consoles may
connect to each UVIC. The consoles may
be placed up to ½ mile away from the
UVIC. The console should be wall
mounted approximately 5’ above the
ground. The UVLOC should also be
mounted as far as possible from the
speaker locations to reduce the potential
for audio feedback during a live P.A.
announcement.
The UVLOC requires a CAT5 cable run
between the UVIC and the UVLOC. An
electrical back box is provided for
mounting the UVLOC either on or
recessed within a wall. Six RJ45
connectors are provided on the UVLOC
interface board for making connections.
A terminal strip is also provided that
accepts bare wire.
Summary of Contents for Personnel Alerting System
Page 49: ...INSTALLATION 49 Figure 5 2 UVIC Cabinet Dimensional Outline Drawing ...
Page 50: ...INSTALLATION 50 Figure 5 3 UVIC Wiring Diagram ...
Page 51: ...INSTALLATION 51 Figure 5 4 UVIC Battery Connections ...
Page 62: ...INSTALLATION 62 Figure 5 5 Yagi Antenna Installation Example ...
Page 63: ...INSTALLATION 63 Figure 5 6 Omni Antenna Installation Example ...
Page 64: ...INSTALLATION 64 Figure 5 7 Antenna Grounding Example ...
Page 69: ...INSTALLATION 69 Figure 5 10 UVLOC Dimensional Outline ...
Page 70: ...INSTALLATION 70 Figure 5 11 UVIC25SD Field Wiring Diagram ...
Page 83: ...83 Figure 9 1 UVIC Final Assembly and Parts List Page 2 of 2 ...
Page 84: ...UVIC Final Assembly and Parts List 84 Figure 9 2 UVIC25ST Wiring Detail ...