18
Federal Signal
signaling.fedsig.com
Removal/attachment of the reset keyway is easily done by use of a M2 hex wrench mated to the M4 set screw below the
triangular directional status indicator. The set screw need not be fully removed from the keyway, only loosened enough
to lift the keyway along with the bearing washer from the unit’s status indicator.
Installing/Servicing the Optional Cover Flap
An optional, clear, polycarbonate cover flap is provided either factory-attached on the CP-PB and CP-BG stations or as a
field-installable kit. The cover flap may also be ordered with a clear instructional label attached (e.g., IN CASE OF FIRE
LIFT COVER BREAK GLASS, IN CASE OF FIRE LIFT COVER PUSH BUTTON, TO ACTIVATE LIFT COVER BREAK GLASS, and
TO ACTIVATE LIFT COVER PUSH BUTTON). The IN CASE OF FIRE LIFT COVER BREAK GLASS marking must be present on
EN54-11 certified models.
To remove or remove/reattach a cover flap:
1.
Remove the front faceplate per directions found earlier in ”Call
Point Front Chamber Access” on page 5. Place the two
stainless steel pivot pins of the cover flap within the slot found
on the backside of the faceplate, and rotate the cover 180° to
snap the cover flap onto the front face.
2.
Reattach the faceplate (See “Opening / Closing the Call Point
for Internal Access” on page 4), and then open the cover
to reattach the pushbutton and the reset keyway if they are
provided with the station.
3.
Ensure that access to the activation pushbutton or glass panel
is easily accomplished by lifting the cover flap upward.
Figure 25 Cover
Figure 26 Assembly
(3) ALIGN PIVOT PINS OF
COVER FLAP TO SLOTS ON
BACKSIDE OF FACEPLATE
(PB STATION SHOWN)
(2) REMOVE FACEPLATE BY
UNLOOSENING TWO M4 SCREWS
(4) RE-ATTACH FRONT
FACEPLATE ASSEMBLY
TO HOUSING BY
TIGHTENING TWO
M4 SCREWS
(1) REMOVE
PUSHBUTTON,
RESET KEYWAY &
BEARING WASHER
FROM FACEPLATE
FRONT
(5) SNAP FRONT TAB OF COVER FLAP ONTO FACEPLATE
RELIEF AFTER INSTALLING PUSHBUTTON AND RESET
KEYWAY W/BEARING WASHER