Special applications (e.g., language, specific artwork, site location, etc.): The faceplate’s labeling surface
will accept user-supplied Uline 1.75-inch by 1/2-inch weather resistant labels for laser printers, Uline part #
S-19297.
•
Custom stainless steel Duty Label (separate service part # for field installation): Side mounted on either PB or
BG units (except BG units that have a break glass hammer bar already installed). Consult the factory for lead
times, as this is a customized part for user-specific installation.
Model CP-PB Call Point Push Button activated
•
1-3/4-inch (44.5 mm) diameter spring return black thermoset plastic push button
•
Protective faceplate wall shroud about the button and status indicator
•
Optional bi-color LED status light indicator
Model CP-BG Call Point Break Glass activated
•
Replaceable break glass panel covered with a protective polyester label to limit
glass particle fallout
•
Protective faceplate wall shroud about the status indicator
•
EN 54-11 approved British Standard model available (NOTE: Reset Keyway must
not be installed during operation)
•
Optional side mounted break glass hammer bar
•
Optional bi-color LED status light indicator
Federal Signal Manual Call Point Stations are available with the following optional features factory installed:
•
6 V, 12 V, 24 V or 48 V LED bi-color status indicator
•
High-impact-resistant clear polycarbonate cover flap with or without various instructional labels (e.g., LIFT COVER,
BREAK GLASS TO ACTIVATE) on interior face of the cover flap
•
Side mounted stainless steel break glass hammer bar on BG stations
•
Single and dual switches
•
EN54-11 certified Break Glass stations
Federal Signal Manual Call Point Station may be field serviced with the Service/Accessory Kits specified within Table 2
on “Table 2 Call Points Field Installed Service/Accessory Kits” on page 23.
Unpacking the Call Points Station
After unpacking the station, examine it for damage that may have occurred in transit. If it has been damaged, do not
attempt to install or operate it. File a claim immediately with the carrier, stating the extent of the damage. Carefully
check all envelopes, shipping labels, and tags before removing or discarding them. If any parts are missing, please call
Federal Signal Customer Support at +1 708-534-4756 or +1 800-446-6809.
Opening / Closing the Call Point for Internal Access
The Federal Signal Call Point stations have two chambers within their designs, the first being a front chamber housing
the stainless steel mechanical hardware, and the rear chamber housing the activation switch and an internal wiring block
with housing provisions for M8 or 1/4-inch mounting hardware through the four corner slotted openings.
NOTE:
The design is such that the rear chamber may be accessed with no need to open the front chamber.