Federal Signal

 signaling.fedsig.com

Manual Test and Reset Operation of the Station

The CP-PB and the CP-BG stations have separate activation techniques for placing the internal switch into the alarm 

state and resetting the stations to normal after the alarm state. Follow the instructions according to your station type.

CP-PB Stations

Activation Test

For the manual pushbutton stations, activation is accomplished by a front force directly inward towards the station 

against the black pushbutton, locking the pushbutton in an alarm state. Upon doing so, the activation indicator with a 

reset keyway on the front face located directly below the pushbutton will rotate approximately 60° clockwise, positioning 

itself in the direction of the ALARM state away from the NORMAL standby state. Ensure that the proper switch activation 

has occurred and that the associated control panel is in alarm mode for the station. 

Figure 14  CP-PB States

MODEL CP-PB: ALARM STATE

APPLIED

FORCE

MODEL CP-PB: NORMAL STATE

ACTIVATION

INDICATOR STATUS

POSITIONS

VISUAL 

ACTIVATION 

INDICATOR 

WITH RESET 

KEYWAY

ALARM STATE ACTIVATED

Reset Test

For the manual pushbutton stations, resetting is accomplished by rotating the activation indicator approximately 60° 

counterclockwise by use of a reset keyway that is mated to the activation indicator. Upon rotating counterclockwise, 

the pushbutton knob, along with the internal switch, will be released from the activated ALARM states and return to the 

NORMAL standby positions as noted on the station’s front faceplate. Ensure that the proper switch deactivation has 

occurred and that the associated control panel returns to normal standby mode for the station.

CP-BG Stations

Activation Test

For the manual break glass stations, activation may be accomplished by either of two means:

1. 

Applying a front force directly inwards towards the station against the glass panel, which is noted with BREAK 

GLASS PRESS HERE along with a corresponding target dot to apply the force to break the glass panel. A polyester 

label is attached on the glass panel to protect the user from glass particles when the panel is broken. Once 

broken, the unit must have the panel replaced for resetting it.

Summary of Contents for CP-PB Series

Page 1: ...stallation test the station and the system to ensure that it is operating properly After testing is complete provide a copy of this instruction sheet to all personnel Establish a procedure to routinel...

Page 2: ...11 certification 3 To enable correct installation and operation review all sections in this manual 25500424A for all technical installation and maintenance data UL C UL Signaling Certification Inform...

Page 3: ...einforced polyester GRP thermoset plastic housing and faceplate for corrosion resistance 40 C to 70 C ambient operational coverage Static dissipative GRP housings and faceplates One or two switches av...

Page 4: ...d 6 V 12 V 24 V or 48 V LED bi color status indicator High impact resistant clear polycarbonate cover flap with or without various instructional labels e g LIFT COVER BREAK GLASS TO ACTIVATE on interi...

Page 5: ...inter Figure 1 Removing the keyway UNLOOSENM4SETSCREW TOREMOVERESET KEYWAYANDBEARING WASHERIFPRESENT UNLOOSENTWOM4 CAPTIVATEDSCREWS REMOVE BUTTON ANDSCREW Figure2 ACTUATORSPRING PIVOTBOSSES CLEAR ACTU...

Page 6: ...Chamber Access All models of the Call Point station have the same rear chamber access method for internal wiring management mounting the unit to a vertical wall surface and general maintenance routin...

Page 7: ...accordance with the installation instructions and local jurisdictions and codes Use installer supplied fasteners suitable for the mounting surface All models of the Call Point station have the same re...

Page 8: ...corrosive environment applications mounting the station to a rigid surface Ensure that all cable glands and stopping plugs are certified with a suitable sealing washer o ring to ensure the NEMA IP ra...

Page 9: ...on the aluminum mounting bracket and remove it from the rear housing taking care as it still remains directly wired to the front housing assembly 2 Strip the incoming wiring leads to the station to t...

Page 10: ...ull double throw switch device on a double pull double throw device input terminals 6 7 and 8 are used as secondary inputs with common Figure 8 Standard SPDT switch wiring Figure 9 Standard DPDT switc...

Page 11: ...tivation current draw of 13 mA of the red alarm state LED function will not interfere with the alarm notification panel If it does the hookup of the red LED lead must be disconnected from the terminat...

Page 12: ...990 00 1320 00 3300 411 41 767 44 1164 71 1650 00 4700 427 27 824 56 1301 54 1938 75 5000 429 62 833 33 1323 53 1987 95 5600 433 61 848 48 1362 16 2076 40 10000 448 90 909 09 1525 42 2481 20 12000 452...

Page 13: ...ATE ACTIVATION INDICATOR STATUS POSITIONS VISUAL ACTIVATION INDICATOR WITH RESET KEYWAY ALARM STATEACTIVATED Reset Test For the manual pushbutton stations resetting is accomplished by rotating the act...

Page 14: ...s resetting is accomplished by either of two methods following the previously mentioned two methods of activating the stations 1 To replace the broken glass panel follow the directions on page 16 Once...

Page 15: ...re some important safety instructions and precautions you should follow with regards to all instructions within this manual Read and understand all instructions before operating this system If you acq...

Page 16: ...this manual to do so Replacing the Break Glass Panel CP BG units To replace a broken glass panel on the station CUTTING HAZARD Safety gloves are required when accessing the internal front chamber with...

Page 17: ...DELS Installing Servicing the Reset Keyway The reset keyway is factory attached on the CP PB and CP BG stations On the CP BG x x x xxx xx 2 E54 11 approved stations it is provided separately to be use...

Page 18: ...ertified models To remove or remove reattach a cover flap 1 Remove the front faceplate per directions found earlier in Call Point Front Chamber Access on page 5 Place the two stainless steel pivot pin...

Page 19: ...es resistor along with two wire ties Tools needed after internal access Wire cutter 1 Philips screwdriver To service the module 1 Ensure that the power is off and the station is in NORMAL mode 2 Open...

Page 20: ...reseat the module in its reliefs screw it in place and try again e After confirming that the station actuates properly use the two wire ties provided within the kit to bundle and tie the switch wires...

Page 21: ...station faceplate s designated label area Make sure the application area is free from any dirt smudges or oil prior to application Figure 31 Installing the label OPTIONALINDIVIDUALSTAINLESSSTEELFACEP...

Page 22: ...ion of hazardous atmospheres disconnect the fixture from the supply circuit before opening EXPLOSION HAZARD Substitution of any component may impair suitability for Class I Division 2 Service Technica...

Page 23: ...used with 24V LED option 2 2K 2200 2 4K 2400 3 3K 3300 also used with 48V LED option 3 6K 3600 4 7K 4700 5 6K 5600 10K 10000 12K 12000 15K 15000 22K 22000 33K 33000 47K 47000 Potted Diode Module 5A K...

Page 24: ...g com signaling fedsig com Part Description Federal Signal Part Use Faceplate Label EN54 11 K71400701A CP BG x x x xxx xx 2 EN54 11 stations Faceplate Label Stainless Steel FIRE K71400976A 01 CP BG an...

Reviews: