11
Federal Signal
signaling.fedsig.com
Figure 10 Snap fit clips
FLEX TABS
OUTWARD TO
INSTALL IN PLATE
RESISTOR AND DIODE MODULE
MOUNTING LOCATIONS (2)
FLEX TABS
TO SECURE
MODULE(S)
TO REAR
MOUNTING
PLATE
Optional Bi-Color LED Module Wiring
For the SPDT and DPDT models with an optional factory wired, voltage dependent (6, 12, 24, 48 Vdc), bi-color LED
module and series resistor module added to the front housing (having green illumination in the standby “Normal” mode
and red within the “Alarm” state), please note the following applicable requirements for these specific models:
•
Ensure that the additional activation current draw of 13 mA of the red alarm state LED function will not interfere
with the alarm notification panel. If it does, the hookup of the red LED lead must be disconnected from the
terminations block. Failure to observe this warning may lead to property damage, serious injury, or death.
•
When using with a fire alarm control panel, the panel is to be limited to 5 A maximum. An LED, EOL, or series
resistor may require a compatible control panel.
Figure 11 SPDT with optional
series device module wiring
Figure 12 DPDT switch with
optional EOL resistor module wiring
Figure 13 DPDT switch with
optional LED module wiring
Fire Alarm Control Panel (FACP)
For Federal Signal Call Points stations (Model CP-PB and CP-BG), a compatibility check must be made of the station(s)
when installed to a FACP.