Page 85 of 91
Rev. 4.20
Settings for delayed zone:
N°
STEP BY STEP
DESCRIPTION
CHAPTER
1
MENU
Push the button relative at the “Menu”.
2
ZONE
Select “ZONE” item.
8.3.1
3
view/mod.
Select “view/mod.” item.
8.3.2
4
LOOP SELECTION
Select loop for the zone.
8.3.3
5
ZONE ADDRESS
Insert the address to the zone which you want to
assign the delay output.
8.3.4
6
DELAYED OUTPUT = YES
Set up the validity field to the “DELAYED OUTPUT”
with “YES” value.
8.3.5
Output delay setup:
N°
STEP BY SETP
DESCRIPTION
CHAPTER
1
MENU
Push the button relative at the “Menu”.
2
OUTPUT
Select “OUTPUT” item.
9.1.1
3
view/mod.
Select “view/mod” item.
9.1.2
4
CONTROL PANEL OUTPUT
/
LOOP OUTPUT
Select the item, in which there is the output to
program.
9.1.3
5
OUTPUT SELECTION
Select the loop (if it is loop output) and output
address to program.
6
OUTPUT SETTING
Inside this menu there are all the parameters of
the output.
9.1.4
7
ACTIV. DELAY
Set up the validity field of command for “ACTIV.
DELAY” With the delay value you wish to assign that
output.
9.1.4
17.8 RESET MODE of FIRE ALARM
The “Reset” button on the keyboard of the Panel allows to reset all events which are no longer pending (the ones
who do not have “!” symbol on the second line of description reading).
Once the alarms have been restored, it is possible to set up the reset mode according to the requirements of the
user. See charter 10.4 where all the different modes are explained for programming the reset and restore of all
fire alarms.
Following this, the reset procedure of fire alarm in case of the set up “
F.S. AUTO
” is on display (all points
automatically out of service during the fire alarm).
Restore Fire Alarm:
N°
STEP
DESCRIPTION
CHAPTER
1
Reset
Press button “Reset”.
4.1.1
2
PASSWORD 2
Insert password level 2.
3
Restore alarms
The Control Panel will restore all alarms and
events which have been reset in automatic
(
the
ones who do not have “!” symbol on the second
line of description reading
).
10.1
4
All points in fire
alarm out of service
In restoration phase, the Control Panel will find
all points in fire alarm which have not been
automatically reset and will put all the points
still in alarm into out of service.
10.2
5
Out of service zone in
fire alarm
If all points of a zone are put into out of
service; also the zone will be put out of
service.
10.2
In the case that the zones have been put out of service as a result of Alarm reset (event which occurs whenever
the points of a zone are put out of service), so one must, before anything, put the zones back into service and
then do the same with the points.