8.3.3 Loop selection
Select the “
Loop
” and confirm with “
Sel.
”, type in “
Canc
” to return to the
“
Zone menu
”.
8.3.4 Zone address selection
The control panel supplies the address of the first addressed zone. Through
the numerical keyboard it is possible to select the address of the point the
user wants to view.
Select “
Ok
” To view the information relative to the selected zone. Select
“
Canc
” to return to the “
Zone menu
”.
8.3.5 Zone setting
ADDRESS
:
the zone and loop addresses (no mod.).
NAME
:
the name of the zone (mod.).
POINTS NUMBER
:
points number of the zone (no mod.).
FAULT POINTS
:
the number of the fault points of zone (no mod.).
O.O.SERV.POINT
: the number of the out of service points of zone (no
mod.).
O.OF SERVICE
:
it indicates if the zone is in out of service (mod.
YES
or
NO
).
DOUBLE CONSENSE
: it is used when the control panel is supervisory mode.
If
NO
, when the detector goes to alarm status, the
control panel go to fire alarm too; if
YES
, the zone pre-
alarm is enabled. The possibility to modify this function
is given provided that there are at least 2 points on the
specific zone. If after deleting of a point, the assigned
zone at double consent has only one installed point,
this parameter value will read
No
(mod.
YES
or
NO
).
DELAYED OUTPUT
: it is used when the control panel is supervisory mode.
If
NO
, the alarm delayed is disabled. If
YES
, the alarm
delayed is enabled.
MAX ALARM DETEC.
: it indicates the maximum number of detectors that
can illuminate the leds in fire case (mod.
2
,
4
,
6
,
8
).
TEST RUN
:
it enables the test function. All points begin to flash
and now it is possible test all points. The alarm
messages from the points only come visualize to the
display. The control panel does not go in alarm mode
(mod.
YES
or
NO
).
RATE-OF-RISE EN
: all heat detectors are enabled at the rate-of-rise mode
(mod.
YES
or
NO
).
RATE-OF-RIS.DIS
: all heat detectors are not enabled at the rate-of-rise
mode (mod.
YES
or
NO
).
SUP.TEMP LEV
:
if set up, all the multi-criteria heat detectors acquire the
Loop selection
•LOOP 1
LOOP 2
LOOP 3
LOOP 4
Sel. Canc
Zone addres.selectio
ADDRESS: 01
Ok
.
Canc
Zone setting
•ADDRESS: 01-1
NAME: FIRST FLOOR
POINTS NUMBER: 015
FAULT POINTS: 000
O.O.SERV.POINTS: 000
OUT OF SERVICE: NO
DOUBLE CONSENSE: NO
DELAYED OUTPUT: NO
MAX ALARM DETECT.: 2
TEST RUN: NO
RATE-OF-RISE EN: NO
RATE-OF-RIS.DIS: NO
SUPERV.TEMP LEV: -
NSUPER.TEMP LEV: -
SUPERV.SMOK LEV: -
NSUPER.SMOK LEV: -
Esc. Pre. Next Mod.