Page 24 of 91
Rev. 4.20
Level 3
The access to level 3 is obtained typing (
33333
).
All the information of the configuration is accessible in this level and any change that concerns the system
configuration proves possible.
Level 4
Access allowed only to the manufacturer.
N.B.: the codes of level 3 and 4 must be used only by the qualified technician to the programming of the
control panel.
4.5 OUT OF SERVICE, FAULT, ALARM MESSAGES
4.5.1 General
The Control Panel communicates externally through:
ü
buzzer (active whenever a new alarm signal has been triggered (alarm or fault);
ü
led;
ü
display.
It communicates in the event of:
ü
fire alarm;
ü
evacuation;
ü
fault;
ü
technological alarm (bath, etc...);
ü
out of service;
ü
active outputs
ü
pre-alarm.
4.5.2 Silence
This function is not necessarily linked to fire alarm, fault or out of service alarm.
When an element (detector, button or module) is activated, the signal of fire alarm with all the necessary
parameters to identify the activated point in the shortest possible time appears on the display. A buzzer inside the
control panel is activated and the read led of alarm signal lights up.
It is possible to silence at once the buzzer inside the control panel pressing the key silence placed.
GENERAL SIREN SILENCE MODE
If you need to silence the siren/s output and/or all the ones enabled to this command, (see chapter
15.3.4), you
must access the “
Evacuation menu
” and press the related command to the voice “
OUTPUTS SILEN.MOD
”.
It is possible to re-instate the silenced outputs by entering “
Evacuation menu
” and press the related command
button at the voice “
OUTPUTS RESTART
”.
SILENCE SINGLE SIREN
If you wish to silence one siren at a time and all ones enabled to this function (see chapter
15.3.4), it is necessary
to access the “
Output setting
” menu , related to the output to silence, and press the “
Sil.
” command. (this
button substitutes the “
Mod.
” seen in the chapter
9.1.4).
It is possible to re-instate the silenced outputs by entering the “
Output setting
” menu, related to the output ,
and press the button “
Act.
” (this button substitutes the “
Mod.
” as seen on the chapter
9.1.4).
4.5.3 View Messages
Whenever the Control Panel reveals a change coming from the main panel or loop, this shall appear on the
display.
The simplify the identification of this message display, the Control Panel will subdivide the messages in type
groups by showing them according to their priority listing:
ü
fire alarm (maximum priority);
ü
evacuation;
ü
fault;
ü
technological alarm;