Page 54 of 91
Rev. 4.20
10.3 EVACUATION
The control panel permits to manage the evacuation and extinguish procedures from control panel or external
input signal. For the evacuation manual starter from the control panel, to see the chapter
PART 13.
EVACUATION
:
enable the evacuation procedure (mod.:
YES
,
NO
).
ALAR->EVACU T.s
: delay time between the alarm signal and the
evacuation activation (mod. range:
000-600
).
EVAC->EXTIN T.s
: delay time between the evacuation activation and
extinguish activation (mod. range:
000-600
).
EXTIN->EVAC T.s
: delay time between the extinguish activation and the
restoration of the evacuation / extinguish, (mod. range:
010-600
).
MANUAL EVACUAT.
: if it is set up at
YES
it permits to start the evacuation
from manual mode; to view as it is possible to manual
start the evacuation, to see the chapter
PART 13
(mod.:
YES
,
NO
).
After the programming has been executed, select “
Esc.
” to return to the “
Main menu
”.
10.4 FIRE RESTORATION
At the restore fire alarm procedure, it is possible to set up the control panel’s supervision towards all the points
which, at the time of restoration/reset, are still in alarm status.
There are 4 types of fire alarm restoration procedures:
ü
“
NORMAL
”: the control panel only restores the points which are no longer under alarm. The fire alarm is
restored only when all the armed points have been reset before the actual “
restore fire
alarm
” procedure has been executed.
ü
“
FORCED
”: the control panel restores all the points which have generated the alarm. If the control panel
still finds other points in alarm, it will return to the fire alarm condition.
ü
“
AUTO. O.O.S.
”: the control panel restores all the points which are no longer under alarm status and
puts all points which are still under alarm into “
out of service
” condition. In this
operational mode, it is possible to reset and check all armed points for a new phase
avoiding that the same points may not go into alarm again.
ü
“
MAN. O.O.S.
”: the control panel only with manual intervention restores the points which are no longer
under alarm. The fire alarm is restored only if all the points have been reset before the
actual command “
restore fire alarm
” procedure has been executed.
MODE
:
allows to select the action of reset of the points under
alarm (mod.: “
NORMAL
”, “
FORCED
”, “
AUTO. O.O.S.
”
and “
MAN. O.O.S.
”).
Once the programming is completed, select “
Esc.
” to return to “
Main menu
”.
Evacuation setting
•EVACUATION: YES
ALAR->EVACU T.s: -
EVAC->EXTIN T.s: -
EXTIN->EVAC T.s: 010
MANUAL EVACUAT.: YES
Esc. Mod.
Fire restoration set
•MODE: AUTO O.O.S.
Esc. Mod.