WARNING: IMPORTANT NOTES FOR THE START UP OF THE CONTROL PANEL
Begin with checking the power supply and battery status.
Run check test to trouble shoot for short circuit or other malfunctions.
•
Push the reset grey button (system fault) placed to the main board.
•
When “
Password request
” appears, refer to chapter
4.4).
LOOP INITIAL SET UP
a) Install the provided isolator with address zero.
b) Install the input/output modules, buttons and detectors (install only the
bases of detectors if you want addressing the detectors with the
“INSTALLATION” modality).
c)
Check the loop status through the suitable procedure.
Enter “
Main menu
”,
à
“
LOOP
”,
à
“
o.o.s/rest
”
à
“
Password
request
”.
à
“
Loop start/restore
”.
à
“
SELECT LOOP
” to decide
which loop is being intended to start, or “
SELECT ALL LOOPS
” to start up all
loops in automatic succession.
There are three start up procedures/loop reset:
•
LOOP RESTART
: to select when isolators are not zero address in loop.
•
INST.ISOLAT.
: to select when isolators are present along
the loop with address zero;
After the start up procedure, check in the menu for the isolators which
“
POINT
”
à
“
view/mod.
” are addressed in succession starting from
addresses 121.
•
OUT OF SERVICE
: to select in case of maintenance of loop or add on
new points.
See the button in the schematic of
chapter
2.5.
Repeat starting procedure for
each loop procedure to reset to
zero address, manual on page 69.
According to the method of
addressing it is possible to install
the detectors: see different
addressing methods, manual
page 33.
To move in the menu see page
22.
The starting procedure with
search isolator of each loop must
be made only once. See manual
on page 31.
When loop has started without any faults, “
COMPLETED OPERATION
” press the “
Ok
” button, otherwise an event
will be caused and the found trouble will be pointed out.
PART 5
FIRST CONFIGURATION OF CONTROL PANEL