Page 47 of 91
Rev. 4.20
To activate the output status of the input/output module set yourself on the
activation line using the four arrows and type in “
Mod.
”.
The output activation of the input/output module allows different possibilities
of programming of the same module. The selection is made typing in “
Mod.
”
and it is viewed with a cross (
x
).
It is possible to activate an output if a particular zone of a loop is in fire
alarm. To do this, it is necessary to select “
ZONE REPETITION
”, to define
the loop and the range of the zone.
By means “
MODE
”, the logical formula can be set up for which the output
must be activated:
-
OR-OR
:
the output is activated when at least a device of a zone goes
in fire alarm;
-
OR-AND
:
the output is activated when at least an entire zone has all
the devices in fire alarm;
-
AND-AND
:
the output is activated when all the zones have all the
devices in fire alarm;
The possibility to do activate an output through a formula, it is not available
now.
Output setting
OUTPUT ADDRESS:001-1
TYPE: LOOP OUTPUT
DEVICE: RELAY
OUT OF SERVICE: NO
FAULT: NO
STATUS: DISABLED
TEST RUN: NO
•ACTIVATION:
FORMULA
FORMULA: NOT AVAILAB
SILENT MODE: NO
ACTIV. DELAY s: -
MAN.ALARM ACTIV:
NO
OUT ACTI.TIME s: -
INVERT:
NO
Esc. Pre. Next Mod.
Output setting
OUTPUT ADDRESS:001-1
TYPE: LOOP OUTPUT
DEVICE: RELAY
OUT OF SERVICE: NO
FAULT: NO
STATUS: DISABLED
TEST RUN: NO
•ACTIVATION:
STATUS
TECHNOLOG.ALARM [ ]
FIRE.PREALARM [ ]
FIRE.ALARM [ ]
EVACUATION [ ]
EXTINCTION [ ]
FAULT [ ]
OUT OF SERVICE [ ]
SILENT MODE: NO
ACTIV. DELAY s: -
MAN.ALARM ACTIV:
NO
OUT ACTI.TIME s: -
INVERT: NO
Esc. Pre. Next Mod.
Output setting
OUTPUT ADDRESS:001-1
TYPE: LOOP OUTPUT
DEVICE: RELAY
OUT OF SERVICE: NO
FAULT: NO
STATUS: DISABLED
TEST RUN: NO
•ACTIVATION:
ZONE REP
MODE: OR-OR
LOOP REPETITION: 1
1st ZONE REPET.: 01
LAST ZONE REPET.: 01
SILENT MODE: NO
ACTIV. DELAY s: -
MAN.ALARM ACTIV:
NO
OUT ACTI.TIME s: -
INVERT: NO
Esc. Pre. Next Mod.