10.1 DETAILS
Inside the “
Setting menu
” there are different items for the control panel programming.
supervis.
:
supervised setting of the control panel.
evacuation
:
evacuation function enabled of the control panel.
fir.restor
:
control panel function in the case of fire alarm restoration.
date/time
:
date and time modification of the control panel.
prompt
:
modification of the two line strings presents on the initial
display.
password
:
modification access password at the levels.
loop act.
:
activation and deactivation of the loops.
re.default
:
restoration of the default setting.
10.2 SUPERVISED / UNSUPERVISED
The supervisory mode is when the control panel is supervisory from the authorized personnel. That is when a
operator can go to control the control panel, if this goes alarm (an example is a hospital). If this is not possible, the
control panel must been in no supervisory mode (an example is the closing time of a company).
In the unsupervised procedure the pre-alarm given by the double consent is not enabled (the user must pass to
the alarm signal directly). To have the pre-alarm in the zones enabled to this property, it will be necessary to be in
supervised procedure.
ENABLED
:
enabled of the supervisory mode (mod.:
YES
=
supervisory;
NO
= no supervisory).
ACTIVE
:
it indicates if now the supervisory status is activated
(no mod.).
START DATE
:
start date of the supervisory mode (mod.).
END DATE
:
end date of the supervisory mode (mod.).
START TIME
:
start time of the supervisory mode (mod.).
END TIME
:
end time of the supervisory mode (mod.).
2^GLOB.CONSENSE
: if it is set up
YES
, the control panel set up the global
consent global (mod.:
YES
,
NO
).
DELAYED F.ALAR.s
: if it is set up, the control panel set up the delay of
output activation in the case of fire alarm (mod. range:
000-600
).
After the programming has been executed, select “
Esc.
” to return to the “
Main menu
”.
PART 10
SETTING MENU
Setting menu
supervis.
password
evacuation loop act.
fir.restor re.default
date/time
prompt
ACCESS LEVEL: 1
Sel. Back Esc.
Supervisory setting
•ENABLED: YES
ACTIVE NO
START DATE: 01/01/00
END DATE: 01/01/00
START TIME: 00:00:00
END TIME: 00:00:00
2^GLOB.CONSENSE: NO
DELAYED F.ALAR.s: -
Esc. Mod.