Page 27 of 35
Rev. 1.03
GENERAL
Case size:
Metal case: base x depth x height 351x95x292mm.
Protection index:
IP40.
Weight:
Metal case: 3.5Kg without battery.
Operating temperature:
-5° / +40°C.
Relative humidity:
95% maximum.
Power supply:
230Vac ±10/-15%, 50Hz.
Max absorption:
50VA.
Power supply fuse:
T 500mA L 250V.
Transformer block output:
34Vac.
24V aux output:
21,5Vdc to 28Vdc.
WARNING
: the 24V aux is protected from a fuse, but it is not supervised. The
control panel does not control the fuse status.
24V aux fuse:
F 315mA L 250V.
Battery charger:
27.6Vdc at 20°C.
Battery:
Lead sealed at Pb 24V – 7,2Ah.
Battery fuse:
T 2A L 250V.
ZONE
Zones:
Control panels from 2, 4 or 6 zones.
Max. number of detectors:
20.
End of line resistor:
3.9K
Ω
1/2W.
Alarm current:
25mA.
Alarm resitor:
220
Ω
2W.
Prealarm resistor:
1K
Ω
1W.
SIREN OUTPUT
Siren output:
2 supervisory siren outputs. Short and open circuit control.
Output 1: alarm.
Output 2: pre-alarm.
Max. current:
250mA.
End of line resistor:
10K
Ω
1/4W.
PART 9