restoration of the control panel.
TEST
Level 2: it lights all leds and internal buzzer for a time of 5s.
Level 3: it permits to put a zone in test mode.
OUT OF SERVICE
Level 2: it permits to set the zone and the siren/relay outputs to out of service.
Level 3: it permits to set the zone as alarm or pre-alarm mode.
SIREN
Level 2: it permits to active the siren outputs.
Level 2, on alarm status, it permits to put the delays to zero of siren output.
Level 3: it permits to set the siren output delays.
LEVEL
It permits to access to 2 and 3 levels.
It permits to escape from menus without modification.
Level 2: it permits to change the password of 2 level.
Level 3: it permits to change the password of 3 level.
3.6 MAINTENANCE
The maintenance measures advised in EN 54-14 must be followed.
3.6.1 Leds/buzzer test
It is possible to execute the leds and buzzer test from the control panel.
Procedure:
•
Access at level 2.
•
Push <
TEST
> button.
This function lights up all leds and it actives the internal buzzer and fault relay for a time of 5s.
3.6.2 Daily control
The user will check that:
ü
The control panel works properly. Otherwise the faults will be reported and registered
and the maintenance staff must be informed.
ü
It is advisable that all or any faults during testing or noted previously, are solved as soon
as possible, for a correct functioning of the control panel.
3.6.3 Weekly control
ü
It is advisable to check the status of disconnected and connected batteries.
ü
A detector or a button will be started up to test the control panel and the connected
fittings of alarm. It is suitable to check a different zone every month.
ü
Where it is admitted, inform the fire brigade or the control centre.
Any malfunctioning must be noted in the event register. The problems must be solved as soon
as possible, in case contacting the installer.
3.6.4 Four-monthly control
The maintenance staff must carry out the following controls:
ü
Look over the notes of the event register.
ü
Examine all the connections of batteries.
ü
Check the alarm functioning, auxiliary fault of the control device and signaller.