Page 17 of 35
Rev. 1.03
5.1.4 Level 3
Access allowed only to the installer. All functions are accessible in this level and it is possible
whichever modification to change every setting: to restore the default configuration, to start the
test function, to set alarm or pre-alarm of the zones and to delay the siren outputs.
Procedure:
•
Push <
LEVEL
> button (the led flashes fast).
•
Insert the password of level 3 (default
333
).
The led <
LEVEL
> is on and it flashes slow.
To abort the procedure, push <
LEVEL
> button.
Procedure to modify the password of level 3:
•
Push <
LEVEL
> button (the led flashes fast).
•
Insert the password of level 3.
•
Push <
LEVEL
> button within 2 seconds (the leds <
TEST
>, <
OUT OF SERVICE
> and
<
SIREN
> flash fast).
•
Insert the new password of level 3.
•
Reinsert the new password of level 3 (a double beep gives the password change; a long
beep gives a change error).
It is not possible to have the password of level 2 equal to level 2.
To abort the procedure, push <
LEVEL
> button.