Page 23 of 35
Rev. 1.03
•
At this step it is possible to active a alarm through a detector or alarm point. The control
panel lights up the <
ZONE ALARM
> led to indicate that zone is alarmed.
•
After about 5s, the control panel restores the alarm signal and it is possible to pass to
other detectors or alarm point.
To finish this test procedure, to push <
LEVEL
> button. The control panel restores all zones.
NOTE: if during the test a zone, that it is not in test, goes to alarm, the control panel finishes
test procedure and it starts that of alarm. The zones that during the test mode were in alarm
status, they are not restore.
NOTE: if during the test the control panel finds a fault signal not from the zones in test, the
control panel finishes test procedure and it starts that of alarm. All zones are restored.
7.3 ZONE PREALARM
It is possible to set a zone in pre-alarm mode, that is the alarm signal activation when at least
two detectors are alarmed.
For all devices that they do not work for absorption (buttons, smoke linear barriers, etc.) which
the user wants to set pre-alarm, it is necessary to use the specific resistor (see chapter
PART
9).
Procedure:
•
Access at level 3.
•
Push <
OUT OF SERVICE
> button. The led <
OUT OF SERVICE
> flashes with quick
intermittence. The <
ZONE ALARM
> and <
FAULT – OOS/TEST
> leds for every zone are
lit if the alarm or pre-alarm the zone is:
o
<
ZONE ALARM
> led is on: alarm.
o
<
GUASTO – FS/TEST
> led is on: pre-alarm.
•
To modify the alarm/pre-alarm status of the zones with the <
ZONE BUTTON
>.
•
To confirm the modification to push <
OUT OF SERVICE
> button.
To interrupt the procedure and return to level 1 without having applied any changes, press
the <
LEVEL
> button.
7.3.1 Automatic activation <Out1>
Of default, the <
Out1
> output is off until the control panel finds a new fire alarm. It is possible
activate the <
Out1
> output after delay of 180s from the pre-alarm:
Procedure:
•
Access at level 3.
•
Push <
OUT OF SERVICE
> button. The led <
OUT OF SERVICE
> flashes with quick
intermittence. With the <
SIREN
> button it is possible change:
o
<
SIREN
> led is on: <Out1> output is activated after a delay of 180s from the pre-
alarm revelation.
o
<
SIREN
> led is off: <Out1> output is disabled (it is activated if the control panel
finds a new fire alarm).
•
To confirm the modification to push <
OUT OF SERVICE
> button.