
10
CONDENSER WATER
OUT
IN
Bulkhead Fittings, Condenser
Figure 5.5
A. Connect a backflow prevention assembly to the water inlet of the unit (see Figure 5.2). A backflow
prevention assembly is available from FBD under PN 12-2272-0001.
B. Fabricate a 3/8 inch supply line for connecting the unit to a potable water supply (a 3/8” barb by 1/4”
flare nut fitting will be required).
C. Install a shutoff valve in the water line as close to the unit as practical and convenient.
The use of
a water filter is recommended.
D. Clear the line by running a minimum of two (2) gallons (7.57 liters) of water through the line before
attaching the line to the unit.
E. Connect the line to the bulkhead fitting labeled “WATER IN” located at the rear of the unit (see
Figures 5.2, 5.3 or 5.4, as appropriate).
F. For water cooled units:
1. Fabricate another water line from the main water line and
connect to the bulkhead fitting labeled “Condenser In” (a
3/8” barb by 3/8” flare nut fitting will be required) (see
Figure 5.5).
2. Fabricate a 3/8 inch drain line for connecting to the
location labeled “Condenser Out” (a 3/8” barb by 3/8” flare
nut fitting will be required) (see Figure 5.5).
G. Route the drain line to a drain location.
H.
Do not turn water on at this time.
5.2 CO
2
SUPPLY
NOTE:
The CO
2
supply may come from either an independent tank/regulator or a bulk CO
2
system. If
connected to a bulk CO
2
system, install a shutoff valve and a secondary supply regulator [to be set at
70-72 psig (482.6-496.4 kPag)] in the line.
Ensure that the CO
2
line comes directly from the main
branch on the bulk supply and is not branched off down line. Failure to do so may starve the unit
of CO
2
flow and cause performance problems.
A. Fabricate a 3/8 inch supply line for connecting the unit to a CO
2
supply.
B. Connect the supply line to the CO
2
bulkhead fitting labeled “CO
2
IN” located at the rear of the unit
(see Figure 5.2). A 3/8” barb by 1/4” flare nut fitting will be required to make connection.
C. Splice a barb “cross” into the CO
2
supply line and run two (2) lines to the syrup pump CO
2
inlets.
Or
If Figal tank will be utilized, splice a barb “cross” into the CO
2
supply line and run two (2) lines to tank
location and install CO
2
tank couplers to end of lines.
D.
Do not turn on the CO
2
at this time.
5.3 SYRUP
SUPPLY
The unit may be connected to either a BIB (Bag-in-Box) or a five-gallon syrup supply (figal). Use the
appropriate connection method below.
NOTE
Installations requiring long runs of tubing [25 feet or more (7.62 meters)] may encounter
pressure fluctuation problems. The machine’s sensors may indicate that the machine is out of syrup,
water, or CO
2
. To avoid pressure fluctuations, consider the following solutions.
A. Increase the tubing size to 1/2 inch diameter.
B. Install booster pumps in the supply lines. Use a vacuum regulating valve with syrup booster
pumps.
C. Increase primary CO
2
regulator pressure from bulk or tank CO
2
to 105 - 120 psig (723.9 to
827.4 kPag). A secondary regulator
will
be necessary for syrup pumps to avoid exceeding
manufacturer’s recommended operating pressures. Set the secondary regulator to 70-72 psig
(482.6-496.4 kPag).
Summary of Contents for FBD562
Page 49: ...49 14 8 LOWER BOARD SCHEMATIC FBD 562 562 ELECTRICAL BOX SCHEMATIC ...
Page 50: ...50 14 9 UPPER BOARD SCHEMATIC FBD 563 563 SCHEMATIC UPPER BOARD ...
Page 51: ...51 14 10 LOWER BOARD SCHEMATIC FBD 563 563 ELECTRICAL BOX SCHEMATIC ...
Page 52: ...52 14 11 UPPER BOARD SCHEMATIC FBD 564 564 SCHEMATIC UPPER BOARD ...
Page 53: ...53 14 12 LOWER BOARD SCHEMATIC FBD 564 564 ELECTRICAL BOX SCHEMATIC LPB1 ...