4-14
Continuously Transmitting/Receiving Measured Values Automatically
4-6 Continuously
Transmitting/Receiving
Measured Values Automatically
Use this function to continuously transmit measured values automatically from the CDX Series.
MEMO
The CDX Series only transmits data from communication port “5010” when this function is used to continuously transmit
measured values.
Writing (starting/stopping continuous transmission)
Sent command (setting the reception port/IP address)
40
02
10
E0
00
08
Reception port number (4 bytes)
Reception IP address (4 bytes)
Reply command
C0
00
Sent command (setting the transmission channels)
40
02
01
E0
00
08
00
00
00
Transmission channel* (1 byte)
00
00
00
00
Reply command
C0
00
* Explanation of bits
8
7
6
5
4
3
2
1
Not used
Not used
Not used
Not used
Channel 4
Channel 3
Channel 2
Channel 1
Example: Specify “5013” for the reception port, “192.168.0.11” for the reception IP address, “Ch1 only” for
the transmission channel, and then start continuous transmission.
Sent command (setting the communication port/IP address)
0x400210E0000800001395C0A8000B
Reply command
0xC000
Sent command (setting the transmission channels and starting the continuous transmission)
0x400201E000080000000100000000
Reply command
0xC000
MEMO
To stop continuous transmission, use the “setting the transmission channels” command to set all the channels to 0 (OFF).