FREQUENCY PROTECTION FUNCTIONS
To be able to trip with any of the protection functions, the setting Function Enable must be set to a value
different to No. We have 2 different options: Alarm or Trip.
In both cases the function will trip, but only if the Function Enable is set to Trip the protection function
will participate in the GENERAL TRIP.
7.1 Function 81U/O. Under/Overfrecuency
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
81_1
81_2
81_3
81_4
Under/Overfrequency
Function Enable
-
-
No/Alarm/Trip
-
No
Type
-
-
(1)
-
Overfrequency
Activation level
45.000
65.000
0.001
Hz
55.000
Time Delay
0.020
300.000
0.001
s
0.200
Reset time
0.020
300.000
0.001
s
0.200
(1)
Overfrequency or Underfrequency
The four functions can be independently configured as overfrequency or underfrequency units.
If the unit is set as overfrequency, activation of the function occurs at 100% frequency level set and its
reset when the measured frequency is 50mHz lower than set start level.
If the unit is set as underfrequency, activation of the function occurs at 100% frequency level set and its
reset when the measured frequency is 50mHz higher than set start level.
The reset time is configurable.
The frequency measurement is done from the voltage of phase B. It has a hysteresis for its activation:
it takes a minimum of 20 volts P-N (35 volts P-P) for 81 functions to be operational. If the measured
phase voltage is less than 15 volts P-N (26 volts P-P), it activates a state bit (
Busbar Frequency Block
)
indicating function blocked. When the frequency measurement is valid again, function begins in the start
state with all bits reset.
The accuracy of the Time Delay is equal to the set time delay ±35ms or ±0.5% (whichever is greater).
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...