COMMUNICATION AND HMI
14.1 Local communication port. USB
An USB port is featured on the front of the device. The connector used is USB connector. The protocol
used is Modbus RTU (115200
–
8 bit
–
no parity
–
1 bit stop).
The ground from the PC should be connected to the same ground as the relay in order to prevent
communication problems.
The USB communication system is insulated from the auxiliary voltage, but not from the shared voltage
of the relay processors, so the cable connecting the PC to the relay should not be excessively long in
order to avoid potential electromagnetic interference with the device.
14.2 Remote communications ports.
14.3 LCD and keypad
The front of the SIL-G relay is fitted with an alphanumeric LCD screen, measuring 20x4. This screen
provides the user with access to read information about the settings parameters, measurements, status
and events. All of this information is arranged in a system of menus.
A keypad is fitted to the relay front panel, which can be used to access the information shown on the
LCD screen and to navigate through the menu system.
This membrane keyboard has 6 keys that can be used to navigate through the different menus and to
change the setting parameters. The ▲ ▼ and ◄ ► keys can be used to navigate through the different
menus, the different options in each menu and the different values for the settings parameters.
The “
OK
” key is used to access the menus and the different options, as well as to approve changes to
values. The “
C
” key is used to delete and to go back through the menu levels.
As well as the 6 keys, there is also a
“
Reset
”
key. When “
Reset
” is pressed, LEDs return to their initial
position. The “
Reset
” key can also be used to delete all of the events in the “
Events
”
menu.
This is equipped with a specific key marked with 79, which permits operation on the recloser, blocking
and unblocking it.
A second specific key marked with 52, which permits operation on the circuit breaker, opening and
closing it.
It is also equipped with a specific key marked with Local, which activate or deactivate the remote
communication of the relay.
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...