4.8 Function 46. Phase balance current protection
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
46
Phase balance current protection
Function Enable
-
-
No/Alarm/Trip/SHB Trip
-
No
Curve Type
-
-
(1)
-
IEC Standard Inverse
Time Dial (TMS)
0.05
25.00
0.01
(2)
1.00
Current Tap
0.050
20.000
0.001
xIn
5.000
Time delay
0.000
300.000
0.001
s
0.200
(1)
Definite time and 8 curves are included to be selected by the user:
TYPE
NAME
DT
Definite Time
IEC
Standard Inverse
Very Inverse
Extremely Inverse
Long Time Inverse
Short time Inverse
IEEE
Moderately Inverse
Very Inverse
Extremely Inverse
(2)
The range of the time Multiplier setting will depend on the curve. The range of this setting for each
curve family is as follows:
TIME DIAL (TMS)
Description
Minimum Maximum Step Unit Default
IEC
Time Multiplier
0.05
1.00
0.01
-
1.00
IEEE
Time Multiplier
0.10
25.00
0.01
-
1.00
If the option
‘Defined
time
’
is selected for the curve setting, the unit behaves like an instantaneous
directional overcurrent unit. In this case, the unit time delay is adjusted by using the parameter
‘Time
delay’
.
If a curve is selected for the curve setting, the time delay depends on the curve, dial and tap settings.
If the unit operates as defined time, the function is activated at 100% of the set tap value, and it
deactivates at 95%.
If the unit operates with a curve, the function is activated at 110% of the set tap value, and it deactivates
at 100%.
The reset is instantaneous in both cases.
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...