Besides, control functions are included as VT supervision, CT Supervision, Trip circuit monitoring or
breaker failure monitoring.
All models include a circuit breaker management block, which:
-
Monitors the condition of the circuit breaker, the number of openings and accumulated amperes.
It generates an indication when there is an excessive number of openings and accumulated
amperes.
-
Determines if an opening fault has occurred
-
Allows circuit breaker opening and closing commands to be given from the HMI (using different
keys) and through local and remote communications
The following measurements are provided by the SIL-G equipment:
-
Phase currents, neutral (measured and calculated), maximum current, positive sequence current
and negative sequence current.
-
Second harmonic current per phase
-
Simple voltages, phase to phase voltages, neutral voltage (calculated and measured), maximum
voltage, line voltage, positive sequence voltage and negative sequence voltage.
-
Current angle for each phase and neutral (referred to VA)
-
Voltage angle per each phase and neutral (referred to VA)
-
Phase B Line voltage angle
-
Active, reactive and apparent powers (3- phase and per phase)
-
Thermal image
-
Line frequency and busbar frequency
-
Rate of change of frequency
-
V/Hz related to nominal Vn/fn
Depending on model, the relay can include different slots regarding inputs and outputs:
The slots 3 and 4 include the inputs and outputs that depending on model offered:
-
SILGxxxxxx0xxx: 7 outputs and 8 inputs. All the outputs and inputs are included in
SLOT 3
, being
SLOT 4
empty.
-
SILGxxxxxx7xxx: 11 outputs and 16 inputs. The 16 inputs are included in the
SLOT 3
and the 11
outputs in the
4
.
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...