Rev.01
142/151
Safe time: 0.020 to 2000.000 s (step 0.001 s)
Locking possibilities: pulse inputs, level inputs, commands.
Function
52
Maximum number of openings: 1 a 100,000 (step
1)
Maximum accumulated amperes: 1 to 100,000 M(A2)
(step 1)
Repetitive number of openings: 1 to 100,000 (step
1)
Time for repetitive number of openings: 1 to 300
min (step 1 min)
Maximum opening time: 0.020 to 300.000 s (step
0.001 s)
Maximum closing time: 0.020 to 300.000 s (step
0.001 s)
Function
74TCS
Function enable: No/Yes
Time delay: 0.020 to 300.000 s (step 0.001
s)
Timing accuracy: ± 30 ms or ± 0.5%
(greater of both)
Function
60CTS
Function enable: No/Yes
Time delay: 0.020 to 300.000 s (step 0.001
s)
Timing accuracy: ± 30 ms or ± 0.5%
(greater of both)
Function
60VTS
Function enable: No/Yes
Time delay: 0.020 to 300.000 s (step 0.001
s)
V1, V2 and VP Tap: 0.08 to 2.00 xUn
(step 0.001xUn)
I1, I2 and 3I0 Tap: 0.010 to 20.000 xIn
(step 0.001xIn)
Timing accuracy: ± 30 ms or ± 0.5%
(greater of both)
Function
50BF
Function enable: No/Yes
Time delay: 0.020 to 1.000 s (step 0.001
s)
Open breaker activation and reset threshold: 8% In
Function
AFD (*)
Function enable: No/Alarm/Trip
Current tap:1 to 20xIn (step 1xIn)
Time delay: 1 to 4 samples (step 1
sample)
Function
86
It allows to latch (lock out) the contact
trip due to programmable logic (PGC: RSFF).
Function
68
Available through configurable inputs and outputs thanks to the
programmable logic (PGC).
Programmable
logic
control
(PGC)
OR, OR_1PULSE, OR_PULSES, OR_BLINKING, OR
_TIMER UP, OR_TIMER DOWN
NOR, NOR_1PULSE, NOR_PULSES, NOR_BLINKING, NOR_TIMER UP, NOR_TIMER DOWN
AND, AND_1PULSE, AND_PULSES, AND_BLINKING, AND_TIMER UP, AND_TIMER DOWN
NAND, NAND_1PULSE, NAND_PULSES, NAND_BLINKING, NAND_TIMER UP, NAND_TIMER DOWN
XOR, OR_1PULSE, XOR_PULSES, XOR_BLINKING, XOR_TIMER UP, XOR_TIMER DOWN
SRFF, SRFF_1PULSE, SRFF_PULSES, SRFF_BLINKING, SRFF_TIMER UP, SRFF_TIMER DOWN
RSFF, RSFF_1PULSE, RSFF_PULSES, RSFF_BLINKING, RSFF_TIMER UP, RSFF_TIMER DOWN
R_EDGE, R_EDGE_1PULSE
F_EDGE, F_EDGE_1PULSE
Settings
tables
4 settings groups
Selectable by input or general setting.
SER
3072 events
Disturbance
fault
recording
(DFR)
32 samples/cycle
Fault start configurable
25 fault reports with 29 events each one
25 COMTRADE records (60 cycles): 1 to 8
pre-fault 52 to 59 post-fault cycles.
COMTRADE IEEE C37.111-1991 - 4 analog channels and 96
digital channels
Load
Data Profiling (LDP)
Demand of power with the following characteristics:
- Number
of records: 2160
- Recording mode circular
-
Sampling rate (interval): configurable through communications (1
-60 min)
Inputs
(*)
Depending on Model:
- 8 configurable inputs
- 8
configurable 4 AFD inputs
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...