![FANOX SIL-G User Manual Download Page 34](http://html1.mh-extra.com/html/fanox/sil-g/sil-g_user-manual_4588716034.webp)
Rev.01
34/151
REVERSE
4.4 Function 50G. Instantaneous measured neutral overcurrent
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
50G
Instantaneous calculated neutral overcurrent
Function Enable
-
-
No/Alarm/Trip/SHB Trip
-
No
Current Tap
0.010
30.000
0.001
xIn
5.000
Time Delay
0.000
300.000
0.001
s
0.200
The time delay is independent from the operating current flowing through the relay, so if the phase
current exceeds its predetermined value for an equal or greater amount of time than this preset value,
the protection function activates (trips) and does not reset itself until the average value of the phase
drops below the point of current pick-up.
The function activates at 100% of the preset input and deactivates at 95%. The reset is instantaneous.
The accuracy of the Time Delay is equal to the set time delay ±35ms or ±0.5% (whichever is greater).
OPERATING ANGLE = 90º
HALF-CONE ANGLE = 60º
HALF-CONE ANGLE = 60º
V polarization
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...