![FANOX SIL-G User Manual Download Page 43](http://html1.mh-extra.com/html/fanox/sil-g/sil-g_user-manual_4588716043.webp)
Rev.01
43/151
If the unit operates as defined time, the accuracy of the Time Delay is equal to the set time delay ±35ms
or ±0.5% (whichever is greater).
If a curve is selected for the curve setting, the accuracy of the time delay is equal to the theoretical time
±30ms or ±5% (whichever is greater).
The curves used are IEC 60255-151 and IEEE, which are described in the corresponding section.
4.9 Function 46BC. Broken conductor detection
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
46BC
Broken conductor protection
Function Enable
-
-
No/Alarm/Trip
-
No
Tap
15
100
1
%
50
Operating time
0.030
300.000
0.001
s
0.200
This protection detects the percentage phase unbalance due to an open phase condition. It considers
the measurement I2/I1 in percentage.
If the measured relation between I2 and I1 is higher (in percentage) than the setting in the function
during the adjusted time, the function will trip.
The function activates at 100% of the preset input and deactivates at 95%. The reset is instantaneous.
The accuracy of the time delay is equal to the set time delay ±30ms or ±0.5% (whichever is greater).
4.10 Function 49. Thermal Overload
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
49
Thermal image
Function Enable
-
-
No/Alarm/Trip
-
No
Current Tap
0.100
2.400
0.001
xIn
1.200
ζ Heating constant
3
600
1
min
3
Cooling constant
1
6
1
ζ heating
1
Alarm
20
99
1
%
80
Thermal image is a measurement of heating and cooling of an electric machine. Contrary to an
overcurrent protection time is not counted when a fault is detected. It continues calculating the thermal
status of the monitored machine. Tripping time depends on adjusted thermal constants, operative
current and previous thermal status of the machine.
Summary of Contents for SIL-G
Page 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Page 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Page 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Page 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Page 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Page 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Page 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Page 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Page 28: ...www fanox com Rev 01 28 151...
Page 69: ...www fanox com Rev 01 69 151 General trip...
Page 88: ...www fanox com Rev 01 88 151...
Page 89: ...www fanox com Rev 01 89 151...
Page 90: ...www fanox com Rev 01 90 151...
Page 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Page 150: ...www fanox com Rev 01 150 151 NOTES...
Page 151: ...www fanox com Rev 01 151 151...