background image

 5  Exemplary configuration of electrical accessories with the ZWMA 

module.

  Blinds were connected to 15VDC (5) power supply and with the use of Primary (6) controller

added to the Z-Wave network. In order to control the blind with the switch (4), also ZWMA module (1) was
added to the same Z-Wave network with the use of LEARN MODE function (see section 4.1 of the manual) as
a Secondary controller. Reverse situation is also possible when the ZWMA module is a Primary controller, then
using additional controllers within the network is not required. Exemplary blind switch chosen by a client (4)
alternately short circuits the proper inputs (here up and down arrows) with appropriate COM input in ZWMA
module (as shown in 

Figure 9). 

Short circuit activates sending appropriate.

13.11.21 NC825-GB

12/16

©2013, 

FAKRO

Figure 9: Adaptive module ZWMA as controller

1. Adaptive module ZWMA.
2. Four control inputs COM1 COM2 COM3 COM4 to which potential-free signals from different external devices can be 
connected, e.g. blind switch, rain sensor, thermostat, KNX/EIB system.
3. Short circuit – activation of potential-free input. ZWMA module sends command “close”, “open” or “stop” to the Z-Wave 
receiver (in this case: ARZ Z-Wave roller shutter).
4. Blind switch.
5. Switched power supply 15 VDC (ZZ60 or ZZ60h) for three electrical accessories.
6. ZWP10 controller (optionally ZWK1, ZWK10, ZWG1 or ZWG3 keyboard).

15V DC

2

3x0,25mm

2

3

1

1

COM

2

COM

3

COM

4

COM

4

2x0,75mm

2

~230V AC

5

6

Summary of Contents for ZWMA

Page 1: ...TE function 8 4 4 Return to default settings of the ZWMA adaptive module DEFAULT function 9 4 5 Removing the ZWMA adaptive module from the network 9 4 6 Additional functions 10 4 6 1 Configuring the Z...

Page 2: ...packing should be kept out of children s reach as thy may be a potential source of hazard The ZWMA module should be used for its intended purpose in agreement with its design The FAKRO Company shall n...

Page 3: ...m the digital input 1 channel 2 operated from the digital input 2 etc ZWMA adaptive module is equipped with a two way radio communication system Z Wave which uses radio frequency of 868 42 MHz Module...

Page 4: ...order to install the ZWMA module it is necessary to 1 Take off the cover terminal of the casing 2 Remount casing to the wall using screws 3 Make all the necessary electric conections 4 Screw the cover...

Page 5: ...that is first deleted from the pair of buttons section 3 4 and then removed from the network section 3 5 The correct implementation of the procedures is to ensure optimal communication between devices...

Page 6: ...o the network long distance between the controller and ZWMA module the module is associated with another network and it is necessary to carry out the DEFAULT procedure first 13 11 21 NC825 GB 6 16 201...

Page 7: ...device operates 13 11 21 NC825 GB 7 16 2013 FAKRO Figure 4 Device associating with selected input In ZWMA module 3 Module is signalling its readiness for associating the device with a selected channe...

Page 8: ...emory is not possible it is desirable to reconfigure the whole network all devices Start a new network configuration from restoring the controller to the factory settings DEFAULT function then call th...

Page 9: ...twork consists in restoring default settings in this module 13 11 21 NC825 GB 9 16 2013 FAKRO Figure 6 Restoring default settings in ZWMA controller Note In the newer version of a controller interrupt...

Page 10: ...the module has been earlier associated with the network as SECONDARY it is necessary to perform DEFAULT procedure 13 11 21 NC825 GB 10 16 2013 FAKRO Figure 7 Removing device from the Z Wave network u...

Page 11: ...another network or has not been assigned to any network It is necessary to perform EXCLUDE function on the device and then again perform INCLUDE and ASSOCIATE functions 13 11 21 NC825 GB 11 16 2013 FA...

Page 12: ...roper inputs here up and down arrows with appropriate COM input in ZWMA module as shown in Figure 9 Short circuit activates sending appropriate 13 11 21 NC825 GB 12 16 2013 FAKRO Figure 9 Adaptive mod...

Page 13: ...nalling of digital inputs LEDs Figure 1 no 5 for digital inputs inform about activation of connected controllers LED for input COM1 lights at short circuit of the contact responsible for sending comma...

Page 14: ...intended use as per user manual Damage is not a result of improperly made electrical system or atmospheric phenomena The manufacturer is not liable for damage which occurred as a result of improper u...

Page 15: ...13 11 21 NC825 GB 15 16 2013 FAKRO...

Page 16: ...FAKRO PP Sp z o o ul W gierska 144A 33 300 Nowy S cz Polska www fakro com tel 48 18 444 0 444 fax 48 18 444 0 333 13 11 21 NC825 GB 16 16 2013 FAKRO...

Reviews: