32
EndURancE 50F
TROUBLEShOOTING & FAq
9. how do I adjust my pilot feed rate settings
(#1 setting)?
not all fuel burns at the same rate. The
moisture content of corn greatly influences how it burns.
Following is a description of the function of the feed trim
button.
Solution:
The auger trim mode on the control board allows the
feed rate on #1 (Pilot setting) to be increased or decreased.
default is level #3. 1 is the lowest feed-rate and 5 is the
fastest. different types of fuel and the way the furnace is
installed will affect the low burn and needs attention during
the break-in period of the furnace.
10. how do I adjust the draft for the Pilot settings
(#1 setting)?
Solution
: Following is a description of the function of the Fan
Trim button. The draft trim mode on the control board al-
lows the draft fan speed to be increased or decreased.
default is level #3. 1 is the slowest and 5 is the fastest. This
may be used in a venting situation that is restrictive, a long
horizontal run or a venting system with excessive elbows for
instance. Before calling your dealer for assistance, please
read your Installations and Operations Manual and perform
all the maintenance issues covered in the daily and Periodic
Maintenance section of the manual. If the furnace still does
not operate correctly, call your dealer for assistance.
11. My Furnace isn’t burning and the controller is
displaying AUGER TIME-OUT.
The unit sensed the au-
ger had not running for more than 2 consecutive minutes.
This can be caused by leaving the hopper lid open or the
unit sensing and over temperature and the fan high limit
switch tripping.
Solution:
Verify the Lid is closed and the switch is operating
properly. Remove fan limit switch cover and ensure the dial
is not above 200 degrees.
12. My Furnace isn’t running and the controller is
displaying ACTUATOR LIMIT ERROR.
The unit sensed
that the actuator did not reach the extended or retracted
position in the allotted time or a wire is broken or discon-
nected from a actuator.
Solution
: Once the unit has cooled down verify the pot is in
-
stalled properly and the remove any obstructions. Go to
the maintenance mode and operate both actuators forward
and back to ensure they move freely. check for any loose,
broken or disconnected wires to the actuators.
Before calling your dealer for assistance, please read your Installations and Operations Manual and perform
all the maintenance issues covered in the Daily and Periodic Maintenance section of the manual. If the furnace
still does not operate correctly, call your dealer for assistance.
FaQ continued...