Page 71
8.10 Level “Configuration” (A parameters)
Automatic change of daylight saving time
Range
Default
A78 Automatic change of daylight saving time
0 .. 3
2
0: deactivated
1: Western European time zone (change at 1:00)
2: Central European time zone (change at 2:00)
3: Eastern European time zone (change at 3:00)
Test parameter for the agitator rating
Range
Default
A80 Rating limit agitator
-1 .. 1
0
-1: more sensitive
0: normal
1: less sensitive
Activate phase monitoring relay ESVAW-003
Range
Default
A85 Activate phase monitoring relay ESVAW-003
0 .. 1
0
0: deactivated
1: activated
Multifunction relay settings
Range
Default
A86 Multifunction relay timer
0 .. 6 0
0: eactivated
d
1: ON delay T1
2: OFF delay T2
3: On and off delay T1 and T2
4: switch-on pulse T1
5: OFF pulse T2
6: Clock T1 on, T2 off
A87 Multifunction time relay input assignment
0 .. 25 0
0: Digital input
1…25 Every output function (A1) can be used as a input signal
A88
Multifunction time relay – T1 time setting
1…5000 sec
30
A89
Multifunction time relay – T2 time setting
1…5000 sec
30
PC-Interface configuration
Range
Default
A95 Baud setting
1 .. 4
4
1: 9600
2: 19200
3: 38400
4: 76800
A96 Device address
1 .. 8
1
Language setting
Range
Default
A98 Language setting for Konsoft
onitor
m
0 .. 1
0
0: german
1: english
8. Setting of parameters