The display board employs a 20 X 4 LCD backlit display for a clear view of data under most lighting 
conditions. Parameters can be adjusted and screens can be navigated using the four membrane 
switches on the front panel. Once the parameters have been configured, the setup menu may be 
locked out to require a four-digit password for further modifications. 

One of the two RJ-45 ports available on the back of the unit is used for connection with the G2 
power controller utilizing a Cat 6 cable, Ionpure

 part numbers IP-CABLE50CM-G2 or IP-

CABLE2M-G2. One display board can independently operate up to sixteen G2 power controllers 
when they are linked together in a daisy chain. 

No external power supply is required with the 

G2 display board.

 

Summary of Contents for IONPURE IP-POWERDSP-G2

Page 1: ...achusetts 01851 Tel 866 876 3340 Fax 978 934 9499 www ionpure com IONPURE G2 DISPLAY BOARD For use with G2 Power Controllers Operation Maintenance Manual IP POWERDSP G2MAN November 2011 Revision 1 Man...

Page 2: ...2 3 2 Connections to Multiple G2 Power Controllers 9 2 4 Power Controller Setup 10 2 4 1 DC Output Current Range Selection 10 2 4 2 Unit ID Selection 11 3 OPERATION 12 3 1 Control Navigation Keys 12...

Page 3: ...Screen Page 2 15 Figure 12 RUN Screen Page 3 15 Figure 13 RUN Screen Page 4 16 Figure 14 RUN Screen Page 5 16 Figure 15 SETUP Screen Page 1 17 Figure 16 SETUP Screen Page 2 18 Figure 17 ALARMS Screen...

Page 4: ...ns has proprietary rights Neither receipt nor possession of this manual confers or transfers any right to the client and by its retention hereof the client acknowledges that it will not reproduce or c...

Page 5: ...oid personal injury or fatalities Cautions indicate a situation that may cause damage or destruction of equipment or may pose a long term health hazard Notes are also used to draw attention to informa...

Page 6: ...parameters have been configured the setup menu may be locked out to require a four digit password for further modifications One of the two RJ 45 ports available on the back of the unit is used for co...

Page 7: ...rovide a seal at the panel cutout and it is secured from the back with the provided nuts The environmental limits for operation are 0 to 50 C at up to 95 relative humidity non condensing Consider the...

Page 8: ...of burrs Figure 3 Panel Cutout Dimensions b Install the display board on the door of the enclosure using the supplied hardware and gasket 2 3 Connections 2 3 1 Connections to a Single G2 Power Contro...

Page 9: ...s to Multiple G2 Power Controllers To connect the G2 display to multiple G2 power controllers a Connect one end of a standard Cat 6 cable to one of the two RJ45 ports on the back of the display b Conn...

Page 10: ...ing excessive current to a CEDI module it is recommended to select an appropriate output current range with DIP switch SW1 of the G2 Power Controller as described in Figure 6 Select the current range...

Page 11: ...hat is connected to a G2 display so they can be recognized without conflicts This is done via rotary switch SW2 of the G2 Power Controller Each SW2 position corresponds to a channel or module MD ident...

Page 12: ...een submenus or configurable setpoints When adjusting a setpoint press to increase the value Hold to increase the value at a higher speed DOWN press to see the previous page of information or select b...

Page 13: ...ine of asterisks Resistance values above 999 9 are represented with HI When the DC output current is zero resistance will be represented with to indicate that resistance can not be measured Channels 1...

Page 14: ...C output current from the power controller to the selected CEDI module Press the ENTER key to adjust this value using the UP or DOWN keys Press ENTER again once the desired value has been set This set...

Page 15: ...t to present Ohms pres Positive values represent an increase in resistance and negative values represent a decrease in resistance in reference to the initial value V AC in actual AC input voltage to t...

Page 16: ...tween terminals Vm Vm of the selected power controller Im VDC estimated value of analog signal between terminals Im Im of the selected power controller PAGE 4 Figure 13 RUN Screen Page 4 Board temp te...

Page 17: ...high resistance limit as follows once the module has come to steady state typically after about 48 hours of actual operating time set the Ohms limit to 1 5 times the steady state electrical resistance...

Page 18: ...commended to use this option to reset all historic data after a module replacement Pressing ENTER will reset the following Op hours value in RUN submenu Ohms init value in RUN submenu Resistance alarm...

Page 19: ...Resistance reports the level status of the actual resistance of the CEDI module The alarm will be ok if the resistance is lower than the value set for Ohms limit in the SETUP submenu it will be hi if...

Page 20: ...LUES Screen VAC maximum registered AC input voltage to the selected power controller AAC maximum registered AC current drawn by the selected power controller VDC maximum registered DC output volts fro...

Page 21: ...er VDC minimum registered DC output volts from the selected power controller to the CEDI module ADC minimum registered DC amps from the selected power controller to the CEDI module Ohms minimum regist...

Page 22: ...f the power controller Display rev firmware revision of the display board Self test a G2 power controller monitors continuously the status of its power stage and temperature sensor The G2 display boar...

Page 23: ...the dilute and concentrate streams through the module 4 For each operating channel on the G2 display enter the RUN submenu and adjust A DC out to set the DC output current to the value calculated by t...

Page 24: ...ler have incompatible firmware revisions Contact parts supplier to update firmware A channel row is blinking Alarm has triggered Access ALARMS submenu to identify the alarm Two or more power controlle...

Page 25: ...ents for Electrical Equipment for Measurement Control and Laboratory Use Part 1 General Requirements EUROPEAN UNION DIRECTIVE The G2 display board was evaluated as an accessory of the G2 power control...